CDA3000 Operation Manual
2-7
2  Mechanical installation
DE
EN
FR
IT
ES
FR
1
2
3
4
5
A
2.5 Push-through 
heat sink (Dx.x)
 
 
Step Action Comment
1
Mark out the positions of the tapped 
holes and the breakthrough on the 
backing plate. 
Cut a tap for each fixing screw in the 
backing plate. 
Dimensional drawings/hole 
spacing see Table 2.6. 
The tapping area will provide 
you with good, full-area contact.
2
Mount the inverter module vertically on 
the backing plate. Tighten all screws to 
the same tightness.
Pay attention to the mounting 
clearances! The mounting seal 
must contact flush on the 
surface.
3
Mount the other components, such as the 
mains filter, line choke etc., on the 
backing plate.
Mains filter max. 20 cm below 
the inverter module
4
Continue with the electrical installation in 
section 3.
Note the following points: 
• Distribution of power loss:  
• The all-round mounting collar must be fitted with a seal. The seal 
must fit flush on the surface and must not be damaged:
(1) Seal  
(2) Tapped hole for EMC-
      compatible contact
(3) Outside
(4) Inside
• The backing plate must be well grounded.
• The best result for effective EMC installation is attained with a 
chromated or galvanized backing plate. If backing plates are 
varnished, the coating must be removed in the area of the contact 
surface!
 
BG3 BG4 BG5
Power loss
Outside (3) 70% 75% 80%
Inside (4) 30% 25% 20%
Protection
Heat sink side (3) IP54 IP54 IP54
Machine side (4) IP20 IP20 IP20
(1)
(4)
(3)
(2)