6-8
Fixed frequency selection for digital inputs
S1IND S2IND S3IND Speed reference Factory setting
1 0 0 20-FF2-1 [27-FF2-2] FF2 = 5 Hz [3 Hz]
0 1 0 23-FF3 FF3 = 15 Hz
1 1 0 24-FF4 FF4 = 30 Hz
0 0 1 25-FF5 FF5 = 3 Hz
1 0 1 26-FF6 FF6 = 0 Hz
0 1 1 30-FF7 FF7 = 50 Hz
6.4 Ramps
31-KSEL Data set selector
The data set selector determines the control factors for data changeover.
Possible control factors for data changeover:
31-KSEL Function Example of application
0 Data set changeover inactive, Standard, factory setting
data set 1 remains
1 Changeover to 2nd data set Heavy load start-up
if: 12-F > 26-FF6
2 Changing over data sets Varying operation
with S2IND from 2 motors to 1 inverter
3 Changing over to 2nd data set Drive with rotation direction
with counter-clockwise
(STL active) dependent load
Two data sets with following parameters are available.
Parameter Data set 1 Data set 2
Minimum frequency 21-FMIN1 28-FMIN2
Maximum frequency 22-FMAX1 29-FMAX2
Fixed frequency 2 20-FF2-1 27-FF2-2
Acceleration ramp 32-RACC1 34-RACC2
Braking ramp 33-RDEC1 35-RDEC2
Voltage increase 42-VB1 45-VB2
Rated voltage 44-VN1 47-VN2
Rated frequency 43-FN1 46-FN2