6-11
46-FN2 Rated frequency [Hz]
Parameter of the 2nd data set. See 43-FN1. See also Fig. 6-6.
47-VN2 Rated voltage [V]
Parameter of the 2nd data set. See 44-VN1. See also Fig. 6-6.
6.6 Special functions
48-IXR Automatic load control (I
R-Compensation)
48-IXR = 0 -> IR Compensation inactive
1-> IR Compensation active with 1st and 2nd data set
2 -> IR Compensation only active with 1st data set
3 -> IR Compensation only active with 2nd data set
Precondition for activation of the IR compensation:
Motor data (Type plate) 50-IN, 51-COS and 52-NN entered for the load
characteristics.
The purpose of the IR compensation is to produce a constant torque
and reduced heating of the motor coil. This is achieved by transplacing
the load characteristics as determined by the characteristics parameters,
by an amount
U
determined by the effective current.
See Fig. 6-7.
IW = 15-IW (Effective current)
IN = 50-IN (Motor rated
current)
COS = 51-COS (cosϕ Motor)
KIXR= 53-KIXR (Correction
factor)
The IR compensation becomes effective from the frequency VBFN. It
is increased linearly: from 0 % at frequency VBFN, to 100 % at frequency
2VBFN. Furthermore it is effective up to 100% (see Fig. 6-8).
U IW IN COS KIXR
=−
()