6-14
53-KIXR Correction factor, I
*
R compensation
The correction factor KIXR corresponds to the resistance measured
between two cables. The correction factor can either be entered or
measured by the inverter.
The measurement is started, if 48-IXR = 1 and 53-KIXR = 0.
The inverter then issues a max. of 1/16 of the device voltage for approx.
2 s or permits the flow of a max. current of 50-IN (entered motor rated
current ). The measured value is automatically stored under 53-KIXR .
Caution:
The motor may turn slowly during the measurement.
54-KSC Slip compensation, correction factor [%]
The correction factor 54-KSC is just like the motor rated slip scaled to
the device rated current.
N
SYN
= Synchron. speed
NN = 52-NN (Motor rated speed)
I
NU
= Inverter rated current
IN = 50-IN (Motor rated current)
COS = 51-COS (cos ϕ)
The correction factor can be either entered or calculated by the inverter.
The calculation is started, when 49-SC = 1 and 54-KSC = 0. The
synchronous speed for the calculation is determined from the rated
frequency 43-FN1. The calculated value is automatically stored under
54-KSC.
55-ISEL Actual control selector [Decimal]
The actual control selector determines the type of current limit regulation.
The controlled dimension is the apparent phase current 14-IS.
55-ISEL Function
0 Current limit control inactive
1 Acceleration / braking ramp current controlled, return of the ramp
function with I > 125% ILIM
2 Acceleration / braking ramp current controlled, ramp stop
at I > 125% ILIM
3 Current injection*
4 As setting 1, but with current injection*
5 As setting 2, but with current injection*
*More detailed information on request
KSC
NNN
N
I
IN COS
SYN
SYN
NU
=
100 [%]