MSP4 / MSP5 / MSP6
P. 4 / 7EM-4854 Rev.8
INSTALLATION
The following is a general procedure for mounting the MSP
to a valve with a yoke and coupling.
Be sure NOT TO CHANGE factory adjusted setting of the
MSP.
Remove power supply during the procedure unless other-
wise specified.
1)
Supply
power to the MSP and apply 0% input (100% for
direct action). Turn the output stem fully clockwise (seen
from the cover).
2) Turn
the valve stem to fully closed position (fully clock-
wise).
3) Set the yoke to the MSP
.
4) Set the coupling to the valve stem and fit the MSP out-
put stem into the coupling. Then fix the yoke and valve
temporarily.
5) F
ix the coupling so that there is no eccentricity between
both stems.
6) F
ix the yoke and valve firmly after checking the eccen-
tricity of both stems again.
7) Attac
h the position indicator if required.
WIRING CONNECTION
Refer to the following diagram when wiring. If an optional terminal box is provided, remove its cover and connect lead-
wires.
MSPx
Bolts (M5)
Position Indicator
Yoke
Lock Nut
Output Stem
Valve Stem
Valve Bonnet
Adjust distance.
Figure 6. Example of the MSP Mounted to a Valve
Remark 1: The yellow wire must be left unconnected if the position output signal is not required. Cut the exposed section of
copper wire and insulate the tip of the wire.
Remark 2: The MSP6 is not provided with full-open/-closed signals.
black (1)
+ (U)
– (V)
+
COM1
+
COM2 COM1
white (2)
red (3)
green (4)
yellow (5)
blue (6)
gray (7)
brown (8)
(1) to (8): Terminal No. of terminal box.
Full-open/-closed signals and forced open/close signals are optional.
POWER
INPUT
POSITION OUTPUT (1 – 5V DC)
FULL-OPEN or
FULL-CLOSED
SIGNAL
(
output stem
)
retracted
(
output stem
)
extended
+ (U)
– (V)
+
COM1
+
COM2
POWER
INPUT
POSITION OUTPUT (1 – 5V DC)
FULL-OPEN or
FULL-CLOSED
SIGNAL
(
output stem
)
retracted
(
output stem
)
extended
COM1
FORCED
OPEN/CLOSE
SIGNAL
FORCED
OPEN/
CLOSE
SIGNAL
(
output stem
)
retract
(
output stem
)
extend
(
output stem
)
retract
(
output stem
)
extend
1
3
2
4
6
5
7
8
11
9
10
• With Both Full-open/closed Signal
and Forced Open/Close Signal
Figure 7. Wiring Diagram
3.2 min. 4.5 max.
3.2 min.
5.9 max.
10
■ WIRING INSTRUCTIONS FOR TERMINAL BOX OPTION
• Other Terminal Box Type• Sequential Control Signal Suffix Code B
Applicable wire size 1.25 mm
2
Remove insulation by 10 mm.