In the event of a black-out, or other situations
resulting in dead voltage potential, will the remote
controlled and interconnected 3-way valves at each
GenSet be de-energized and automatically change
over to the MDO/MGO-position, due to the built-in
return spring. The internal piping on the GenSets
will then, within a few seconds, be flushed with
MDO/MGO and be ready for start up.
MAN Diesel & Turbo
E 11 10 1
HFO/MDO changing valves (V1 and V2)
1624467-7.3
Page 2 (2)
L27/38S, L16/24S, L21/31S, L23/30S, L23/30DF, L28/32S, L28/32DF, V28/32H,
V28/32S, L16/24, L21/31, L23/30H, L27/38, L28/32H