112 Part Number 000014797 Rev02 05/18
Discharge Pressure High Checklist
Improper Installation
Refer to “Installation/Visual Inspection Checklist” on
page 100
Restricted Condenser Air Flow
High inlet air temperature
Condenser discharge air re-circulation
Dirty condenser fins
Defective fan cycling control
Defective fan motor
Improper Refrigerant Charge
Overcharged
Non-condensible in system
Wrong type of refrigerant
Other
Non-Manitowoc components in system
High side refrigerant lines/component restricted
(before mid-condenser)
Freeze Cycle Discharge Pressure Low Checklist
Improper Installation
Refer to “Installation/Visual Inspection Checklist” on
page 100
Improper Refrigerant Charge
Undercharged
Wrong type of refrigerant
Other
Non-Manitowoc components in system
High side refrigerant lines/component restricted
(before mid-condenser)
Defective fan cycle control
NOTE: Do not limit your diagnosis to only the items listed
in the checklists.