9.3.7 IPM malfunction or IGBT over-strong current protection diagnosis and solution (P0)
Error Code
P0
Malfunction conditions When the voltage signals that IPM sent to compressor drive chip
is abnormal, the display LED will show “P0” and AC will turn off.
Possible causes
Wiring error
IPM malfunction
Outdoor fan assembly faulty
Compressor malfunction
Outdoor PCB faulty
Troubleshooting:
For 9K~24K:
Check the wiring between main
PCB and compressor . Are the
wires and connectors broken?
Correct the connection or replace
the wires and connectors.
Yes
No
IPM continuity check. Check if the
IPM terminal resistance values are
uniform.
Replace the IPM board or replace the
main PCB if the IPM board and main
PCB are integrated together.
No
Check if the outdoor fan runs
properly or the outdoor unit
ventilation is good.
Yes
No
Please refer to the solution of
Fan Speed Has Been
Out Of Controlmalfunction
Yes
Check if the compressor resistance
values are uniform .
No Replace the compressor.
Yes
Replace the outdoor main PCB if the
main PCB and IPM are separate.