12
Communication Error Alarm appear on the CBU MASTER display, if there is not communication
between CBU Master and Slave
Master display:
Alarm code
Simbol
Alarm name
Description
0
Emergency stop
Means that the emergency pushbutton is pressed.
2
Alternator failure c.b. D+
If enable, means that battery charger alternator is not detected at engine running D+
3
Missing engine stop
Means that, after engine is stopped, the electronic board detects active parameters
as the engine is still running.
4
Mechanical failure
If generator is running, means that all detected parameters are simultaneously
missing.
9
Pre-alarm analog temperature
Means that the detected temperature by analog sensor rised up over the setted
pre-alarm limit.
10
High engine analog
temperature
Means that the detected temperature by analog sensor rised up over the setted
alarm limit.
12
Pre-alarm analog oil pressure
Means that the detected oil pressure by analog sensor is lower than the setted
pre-alarm limit.
13
Analog low pressure oil
Means that the detected oil pressure by analog sensor is lower than the setted
alarm limit.
16
High level battery
Means that the battery voltage is too high.
17
Low level battery
Means that the battery voltage is too low.
20
Generator: low frequency
Means that the generator frequency is too low.
21
Generator: high frequency
Means that the generator frequency is too high.
22
Generator: low voltage
Means that the generator voltage is lower than the setted alarm thresold.
23
Generator: high voltage
Means that the generator voltage is higher than the setted alarm thresold.
Communication
Error