TROUBLE SHOOTING
30 July 2009 / WHISPER 6/8/11 / US / Copyright © 2009 Mastervolt
Problem Possible cause What to do?
Choked air filter.
Check air inlet openings; clean air filter.
Exhaust blocked.
Check the exhaust system.
Injector blocked.
Have the injector checked.
Loss of compression, sticking or
damaged piston ring.
Have the compression measured.
Clean or replace the rings.
Wear out of cylinder.
Have the compression measured and have the
engine overhauled.
Overload.
Take away the overload.
Low level of cooling oil or air in the
cooling system
Fill up with liquid and release air bubbles.
Check if there are air blocks in the system;
refer to the installation manual
Water inlet system blocked.
Broken impeller.
Water strainer choked
Heat exchanger choked.
Check the cooling system thoroughly.
Broken or slipping V-belt.
Replace and adjust the V-belt tension.
Over-temperature
Faulty thermostat
Check the thermostat or replace.
5.2.3 Warnings
Generator must be shut off immediately if:
Motor RPM suddenly rises or drops.
Unusual noise comes from generating set.
Exhaust gases suddenly colour dark.
Engine failure warning light is on
5.2.4 Service address
If you cannot correct a problem with the aid of the mal-
function table, contact your Mastervolt Service Centre or
Mastervolt Amsterdam for an extended service list, tel: INT
+31-20-3422100.

Table of Contents

Other manuals for Mastervolt Whisper 6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mastervolt Whisper 6 and is the answer not in the manual?

Mastervolt Whisper 6 Specifications

General IconGeneral
BrandMastervolt
ModelWhisper 6
CategoryInverter
LanguageEnglish

Related product manuals