EasyManua.ls Logo

MAXA FD2M42R - Installation Diagram

MAXA FD2M42R
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
age  age 
ote aout luorinated asses
1.
This air-conditioning unit contains fluorinated gasses. For specific information on the type of gas
and the amount, please refer to the relevant label on the unit itself.
2.
Installation, service, maintenance and repair of this unit must be performed by a certified technician.
3. Product uninstallation and recycling must be performed by a certified technician.
4.
If the system has a leak-detection system installed, it must be checked for leaks at least every 12
months.
5.
When the unit is checked for leaks, proper record-keeping of all checks is strongly recommended.
ARI
Appliance shall be installed, operated and stored in a room with a oor area larger than X m²
(Please see the following form ). The appliance shall not be installed in an unventilated space, if
that space is smaller than X m² (Please see the following form ).
Any person who is involved with working on or breaking into a refrigerant circuit should hold a
current valid certicate from an industry-accredited assessment authority, which authorises their
competence to handle refrigerants safely in accordance with an industry recognised assessment
specication.
Servicing shall only be performed as recommended by the equipment manufacturer.
Maintenance and repair requiring the assistance of other skilled personnel shall be carried out
under the supervision of the person competent in the use of ammable refrigerants.
Appliance shall be stored in a well-ventilated area where the room size corresponds to the room
area as specied for operation.
The appliance disconnection must be incorporated with an all-pole disconnection device in the
xed wiring in accordance with the wiring rules.
Appliance shall be stored in a room without continuously operating open ames (for example
an operating gas appliance) and ignition sources (for example an operating electric heater).
R
Refrigerant
Te
Installation
eight (m)
(kgm )
loor Area (m )
0.306
0.6
1.0
1.8
2.2
4
0.68
1.14
2.05
2.50
7
0.90
1.51
2.71
3.31
10
1.08
1.80
3.24
3.96
15
1.32
2.20
3.97
4.85
20
1.53
2.54
4.58
5.60
30
1.87
3.12
5.61
6.86
50
2.41
4.02
7.24
8.85
Max Refrigerant Charge (kg)
R
(kgm )
0.306
0.6
1.0
1.8
2.2
1.224 1.836
29
10
3
2
2.448
51
19
6
4
3.672
116
42
13
9
4.896
206
74
23
15
6.12
321
116
36
24
7.956
543
196
60
40
Min. Room Area (m )
Charge Amount in kg
Minimum Room Area ( m
2
)
Refrigerant
Te
Installation
eight (m)

Table of Contents

Related product manuals