PLUMBING CONNECTIONS
The plumbing connecons must be made in accordance with naonal and/or local regulaons; pipes can be made of steel, galvanised steel or
PVC. Pipes must be accurately sized according to the nominal water ow rate of the unit and the pressure drops of the water circuit. All pipes
must be insulated with closed-cell material of adequate thickness. The chiller must be connected to the pipes using new exible joints, not re-
used ones. The water circuit should include the following components:
Well thermometers to monitor the circuit’s temperature.
Manual gate valves to isolate the chiller from the water circuit.
Metal Y lter and dirt separator (installed on the return pipe) with metal mesh no larger than 1 mm.
Loading group and exhaust valve where necessary.








-







To guaratee correct operaon of the unit, the water must be appropriately ltered (see the instrucons at the start of this paragraph) and there
must be only a minimum amount of dissolved substances. The maximum allowed values are shown below
MAXIMUM CHEMICAL-PHYSICAL PROPERTIES ALLOWED FOR THE CIRCUIT WATER
PH 7,5 - 9
Electrical conducvity 100 - 500 μS/cm
Total hardness 4,5 – 8,5 dH
Temperature ˂ 65°C
Oxygen content ˂ 0,1 ppm
Max glycol quanty 40 %
Phosphates (PO4) ˂ 2ppm
Manganese (Mn) < 0,05 ppm
Iron (Fe) < 0,3 ppm
Alkalinity (HCO3) 70 – 300 ppm
Chloride ions (Cl-) < 50 ppm
Sulphate ions (SO4) < 50 ppm
Sulphide ions (S) No one
Ammonium ions (NH4) No one
Silica (SiO2) < 30 ppm

A recommended connecon diagram is shown bellow.