i-32V5 Air/water inverter heat pumps with axial fansi
45
Defrost led: led ON if defrosng enabled, OFF if defrosng disabled or nished, FLASHING if defrosng me interval count in
progress.
Compressor led: ashes if the compressor is starng, is on if the compressor is acve.
Domesc hot water led: ashes if domesc hot water producon is in progress, is on if COOL+SAN or HEAT+SAN mode is selected
and domesc hot water producon is not in progress.
Led KA resistors: is lit if the anfreeze resistors are acve.
The buons have the specic funcon described below
Select the operang mode and manually reset any alarms.
Each me you press the key you have the following sequence:
OFF -> COOL -> COOL+SAN* -> HEAT -> HEAT+SAN* -> OFF (*= if the sanitary is enabled)
While seng the parameters, this key has the funcon of sending BACK by one level.
Allows you to enter the selected menu to view sub-folders or to set a value (e.g. summer, winter and DHW set-points or various
parameters).
UP key. In the parameter seng mode, it allows you to move to a higher menu or to increase the parameter value
DOWN key. In the parameter seng mode, it allows you to move to a lower menu or to decrease the parameter value
In standard operaon, the display shows the water outlet temperature in tenths of Celsius degrees or the alarm code if at least one is acve. If
several alarms are triggered, the rst one is displayed while the second one will be displayed as soon as the rst one is reset. In menu mode, the
display depends on the current posion
MENU
The following are the main features for navigang the menus, especially describing funcons which are not obvious. The main menu has the
following items:
MENÙ LABEL PASSWORD LEVEL OTHER CONDITIONS
Setpoint Set User Not accessible if connected to Hi-t2
Probes tP Installer ---
Alarms Err User Only if acve alarms
Digital inputs Id Installer ---
Parameters Par Installer ---
Password PSS User ---
Hours of operaon oHr Installer ---
USB USb Installer
Only with pen drive with relevant
update les
Firmware Version Fir Installer Version, Revision and Sub
Alarm log Hist Installer Only if the log contains data
The PSS menu is accessed to enter the service password and to enable access with a higher user permission. When you have exited the menus,
the password must be entered once again to re-enter.
MENÙ SETPOINT
The various setpoints can be viewed and edited.