Page #12 background image
12 AGZ 035A through 065A IOMM AGZ-3
Figure 7, Pressure Drop Curve
03 A-040A
04
A
-060A
06
A
5
5
5
NOMINAL MAXIMUM MINIMUM
Pressure Drop Flow Pressure Drop Flow Pressure Drop Flow
AGZ
Unit
Size
(ft) of Water (gpm) (lps) (ft) of Water (gpm) (lps) (ft) of Water (gpm) (lps)
035AS 9.2 82 5.17 23.1 137 8.62 3.9 51 3.23
040AS 11.5 93 5.87 28.8 155 9.78 4.9 58 3.67
045AS 11.2 106 6.69 28.2 177 11.15 4.8 66 4.18
050AS 13.4 117 7.38 33.6 195 12.30 5.7 73 4.61
055AS 16.2 129 8.14 40.0 215 13.56 7.0 81 5.09
060AS 18.0 138 8.71 45.0 230 14.51 7.7 86 5.44
065AS 10.0 146 9.21 25.1 243 15.35 4.3 91 5.76
Minimum and maximum flows are established to ensure the Delta-T for each unit size falls within the 6 - 16°F range for proper unit control.