EasyManua.ls Logo

McQuay AGZ 030A - Page 49

McQuay AGZ 030A
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IOM 686 AGZ 030A through 065A 49
Cir #2 Starts - Counts the number of starts for circuit #2. Note: If power is lost to the
controller, this data is lost and will start counting over. When power is applied and kept on, the
controller will allow 10 starts for circuit #1 as the lead circuit, then will switch to circuit #2 for
the next 10 starts, etc (Automatic Lead/Lag).
Occupied - |= On, 0 = Off
Flow Failure - |= Alarm, 0 = Normal
OA Lockout - Indicates whether your in OA lockout (see OA Lockout SP). No alarm.
Cir#2Lead=On - Indicates which circuit is in the lead e.g., ½= On, 0 = Off indicates that circuit #2 is
in the lead.
Pmp/Stp #1=0 - |= Auto, circuit #1 allowed to run if cooling capacity is needed, 0 = Pump down
circut #1 and stop.
Pmp/Stp #2=0 - |= Auto, circuit #2 allowed to run if cooling capacity is needed, 0 = Pump down
circut #2 and stop.
Solenoid #1 - On a call for cooling on circuit 1, the solenoid is energized and opened.
Solenoid #2 - On a call for cooling on circuit 2, the solenoid is energized and opened.
Frzstat#1Alm - If circuit #1 fails on freeze, the alarm light on the ZT will light. To clear the alarm,
the Freez-Stat Reset button (located on the Control Panel) must be pushed once to clear.
Frzstat#2Alm - If circuit #2 fails on freeze, the alarm light on the ZT will light. To clear the alarm,
the Freez-Stat Reset button (located on the Control Panel) must be pushed once to clear.
MinLowPres#1 - If circuit #1 falls below the Minimum Low Pressure Setpoint (default is 10 psig) -
Differential (default is 5 psig) the ZT alarm will light. Once it increases above the Minimum Low
Pressure Setpoint, the alarm will clear.
MinLowPres#2 - If circuit #2 falls below the Minimum Low Pressure Setpoint (default is 10 psig) -
Differential (default is 5 psig) the ZT alarm will light. Once it increases above the Minimum Low
Pressure Setpoint, the alarm will clear.
Compressor #1 - Compressor 1 is On or Off
Compressor #2 - Compressor 2 is On or Off
Stage 3 to 6 - Indicates how many additional compressor (or unloading) stages are on at the time.

Table of Contents

Related product manuals