D3 Maximum duration of defrost cycle U min 10 1 40 1
D4 Defrost interval time U min 45 0 199 1
D5 Delay before defrosting U sec 0 0 1990 10
D6 Delay after defrosting U sec 120 0 1990 10
COOL MODE ANTIFREEZE Type Unit Default Min Max Resolution
A1 Antifreeze heater set-point U °C ( F) 5 (41) -40 (-40) 40 (104) 1
A2 Antifreeze heater differential U °C (°F) 2 (3.6) 0.4 (0.7) 10 (18) 0.1
A3
Antifreeze sensor select
0=Leavin
g
water, 1=Enterin
g
wate
r
U Flag
0
(
leavin
g)
01
1
A4 Antifreeze alarm set-point U °C F) 3 (37) -40 (-40) 40 (104) 1
A5 Antifreeze alarm differential U °C (°F) 2 (3.6) 0.4 (0.7) 10 (18) 0.1
ALARM AND CONTACT
Type Unit Default Min Max Resolution
P1 Flow switch confirmation time U sec 5 0
199 1
P2 Flow switch alarm delay at pump start U sec 120 0 199 1
P3 Low pressure alarm delay at compressor start
-
up U sec 30 0 199 1
P4 Comp overload alarm reset type U Flag 0 0 1 1
0=Manual reset, 1=Auto reset
(
manual
)
P
5
High pressure alarm reset type U Flag 1 0 1 1
0=Manual reset, 1=Auto reset
(
auto
)
P6 Low pressure alarm reset t
y
pe U Fla
g
10 11
0=Manual reset, 1=Auto reset
(
auto
)
P7 Fan overload alarm reset t
yp
eUFla
g
10 11
0=Manual reset, 1=Auto reset
(
auto
)
P
8
Pum
p
overload alarm reset t
yp
eUFla
g
00 11
0=Manual reset, 1=Auto reset
(
manual
)
P9 Flow switch alarm reset t
y
pe U Fla
g
00 11
0=Manual reset, 1=Auto reset
(
manual
)
P10 Auxiliar
y
alarm reset t
y
pe U Fla
g
10 11
0=Manual reset, 1=Auto reset
(
auto
)
P11 Antifreeze alarm reset t
y
pe U Fla
g
10 11
0=Manual reset, 1=Auto reset
(
auto
)
P12 Comp overload contact type U Flag 0 0 1 1
0=Normally close (NC)
1=Normall
y
o
p
en
(
NO
)
(NC)
P13 Hi
g
h pressure contact t
y
pe U Fla
g
00 11
0=Normally close (NC)
1=Normall
y
o
p
en
(
NO
)
(NC)
P14 Low
p
ressure contact t
yp
eUFla
g
00 11
0=Normally close (NC)
1=Normall
y
o
p
en
(
NO
)
(NC)
P15 Fan overload contact t
yp
eUFla
g
00 11
0=Normally close (NC)
1=Normall
y
o
p
en
(
NO
)
(NC)
P16 Pum
p
overload contact t
yp
eUFla
g
00 11
0=Normally close (NC)
1=Normall
y
o
p
en
(
NO
)
(NC)
P17 Flow switch contact t
y
pe U Fla
g
00 11
0=Normally close (NC)
1=Normall
y
o
p
en
(
NO
)
(NC)
P18 External alarm contact t
yp
eUFla
g
00 11
0=Normally close (NC)
1=Normall
y
o
p
en
(
NO
)
(NC)
P19 Defrost end contact t
yp
eUFla
g
00 11
0=Normally close (NC)
1=Normally open (NO)
(NC)
35

Other manuals for McQuay MAC 100 CR

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay MAC 100 CR and is the answer not in the manual?

McQuay MAC 100 CR Specifications

General IconGeneral
BrandMcQuay
ModelMAC 100 CR
CategoryChiller
LanguageEnglish

Related product manuals