11
Noise LevelNoise Level
1/1 Octave A-weighed sound pressure level (dBA), ref 20 µPa
125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz Ave.
Model
H M L H M L H M L H M L H M L H M L H M L H M L
MCC 010 C/CR
27 25 21 31 29 25 34 32 28 35 32 27 30 27 22 24 20 15 12 10 8 39 37 33
MCC 015 C/CR
28 25 22 34 31 26 36 33 29 35 32 27 32 29 23 26 21 16 14 12 10 41 38 33
MCC 020 C/CR
30 29 27 37 35 32 40 38 36 38 36 33 37 35 32 29 27 23 21 18 15 44 43 40
MCC 025 C/CR
32 31 27 37 36 32 41 40 37 38 37 34 38 37 33 32 31 30 23 22 21 46 44 41
MCC 030 C/CR
62 60 59 62 59 58 58 57 55 55 54 52 53 51 51 46 44 44 39 37 35 61 59 57
MCC 040 C/CR
61 60 58 64 58 58 59 57 54 55 53 53 54 52 51 45 42 41 35 33 32 61 59 58
MCC 050 C/CR
62 58 58 60 60 59 59 59 57 57 56 56 56 55 55 49 48 48 41 40 39 62 61 60
MCC 060 C/CR
62 57 57 61 59 57 61 59 58 57 56 55 55 54 53 48 47 47 42 41 40 62 61 60
MICROPHONE POSITION :
MCC010 ~ 025 C/CR – 1.4 BELOW THE CENTRE OF THE UNIT.
(WITH 2m LENGTH DUCT AT THE AIR OUTLET)
MCC030 ~ 060 C/CR – 1m INFRONT AND 1m BELOW THE UNIT.
(WITH 4.57m LENGTH DUCT)
Operation RangeOperation Range
Cooling
Heatpump
Heating Cooling
Outdoor temp. (°CDB)
Indoor temp. (°CWB)
-5
19
35
15
46
24
54
STD
HIGH AMBIENT
UNIT
LOW AMBIENT
KIT
Outdoor temp. (°CWB)
Indoor temp. (°CDB)
-8
15 21
6
27
18
STD
Outdoor temp. (°CDB)
Indoor temp. (°CWB)
-5
19
35
15
46
24
54
STD
HIGH AMBIENT
UNIT
LOW AMBIENT
KIT

Related product manuals