Model : MCK030B / MLC030B
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46
26.7 13.9 TC 6.802 6.553 6.33 6.108 5.885 5.618
SC 6.802 6.553 6.33 6.108 5.885 5.618
15 TC 7.619 7.206 6.838 6.469 6.1 5.658
SC 6.593 6.339 6.113 5.887 5.661 5.39
18 TC 9.849 8.989 8.221 7.454 6.686 5.765
SC 6.022 5.758 5.522 5.286 5.051 4.768
19.4 TC 10.889 9.821 8.867 7.913 6.959 5.815
SC 5.756 5.486 5.246 5.006 4.766 4.477
20 TC 11.335 10.226 9.235 8.244 7.254 6.065
SC 5.641 5.366 5.121 4.875 4.629 4.335
22 TC 12.822 11.574 10.461 9.348 8.234 6.898
SC 5.261 4.966 4.702 4.439 4.176 3.859
24 TC 14.308 12.923 11.687 10.451 9.215 7.731
SC 4.881 4.565 4.284 4.003 3.722 3.384
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB,
please use the formula below :
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Where, BPF = Bypass factor
EDB = Entering dry bulb temperature, ° C
MCK015B
MLC015B
MCK020B
MLC020B
MCK025B
MLC025B
MCK030B
MLC030B
Bypass factor 0.67 0.16 0.26 0.21