16
MODEL
WATER
FLOW
W.P.D
ENTERING AIR: DB28ºC, WB21ºC
ENTERING WATER TEMPERATUREºC
6 7 8 9 10
TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE
W W W W W W W W W W
0.24
0.51 2376 1738 2220 1671 2110 1553 2004 1560 1716 1444
0.33 0.96 2663 1891 2443 1774 2338 1758 2111 1775 1995 1656
0.42
1.56 2885 2051 2671 1890 2443 1880 2338 1911 2112 1808
0.51 2.29 3002 2157 3018 2000 2663 1982 2449 1985 2223 1889
0.36 2.19 3553 2629 3330 2496 3082 2330 2898 2394 2750 2280
0.48 3.89 3934 2805 3554 2656 3388 2616 3051 2646 3036 2495
0.6 6.08 4246 3007 3910 2770 3554 2780 3345 2814 3163 2687
0.72
8.76 4396 3188 4185 2920 3858 2953 3511 2972 3330 2798
0.42
3.08 4466 3256 4165 3096 3933 2892 3713 2982 3146 2817
0.6 6.29 5107 3506 4633 3467 4438 3413 4001 3486 3773 3293
0.78 10.6 5584 3963 5300 3690 4675 3720 4460 3780 4023 3596
0.96 16.1 5821 4144 5540 3880 5151 3914 4693 3980 4245 3798
0.72
10.04 7150 5203 6692 5025 6263 4742 5875 4884 5214 4550
0.9 15.69 7682 5206 6917 4964 6571 4834 5943 4904 5606 4616
1.08 22.59 8129 5504 7428 4960 6790 4997 6408 5082 5774 4878
1.26
30.75 8359 5706 7941 5310 7342 5334 6698 5460 6021 5161
1.14 5.53 9504 6996 8912 6707 8274 6326 7619 6476 6754 6098
1.44 8.83 10236 6938 9287 6605 8865 6530 8001 6647 7493 6373
1.74 12.89 10872 7459 10067 6940 9107 7041 8660 7140 7812 6706
2.04 17.72
11189 7693 10661 7180 9863 7276 9028 7434 8170 6979
1.2
6.44 10527 6974 9813 7371 9091 7153 8581 7289 7678 6913
1.5 10.1 11299 7735 10238 7344 9721 7276 8751 7392 8165 6999
1.8 14.49 12002 8139 11088 7530 10016 7634 9504 7833 8523 7504
2.1 19.72 12355
8511 11762 7870 10860 7961 9884 8127 8926 7787
1.56 11.21 13090 9152 12220 8807 11389 8359 10675 8635 9460 8244
1.92
16.98 13984 9998 12576 9395 11994 9238 10756 9419 10095 8656
2.28 23.94
14766 10285 13618 9610 12290 9739 11561 9870 10402 9110
2.64 32.1 15120
10561 14383 9790 13260 9892 12062 10059 10809 9433
NOTES:
1) THE COOLING CAPACITY IS TESTED UNDER HIGH SPEED.THE CAPACITY UNDER MEDIUM AND LOW FAN
SPEED MUST MULTIPLY A CORRECTION FACTOR.
2) W.P.D:WATER PRESSURE DROP
TOTAL:TOTAL COOLING CAPACITY SENSIBLE:SENSIBLE COOLING CAPACITY
Cooling Capacity Correction Factors:
MODEL
MEDIUM
TOTAL 0.85 0.82 0.84 0.84 0.87 0.85 0.86
SENSIBLE 0.78 0.75 0.78 0.80 0.80 0.80 0.80
LOW
TOTAL 0.66 0.60 0.65 0.65 0.68 0.70 0.71
SENSIBLE 0.58 0.55 0.58 0.6 0.62 0.63 0.66