-75-
Design & installation Guide For McQuay MDS Multi System
Hot water coil installation
The hot water coil is secured in the air outlet grid of the master unit with rivets
or screws. The connection diagram is as follows:
Make sure supports and hangers are provided to the horizontal and vertical air pipes, and stow-
wood is added between the support or hanger of the insulation air pipe and the insulation layer.
For the distance between the support and hanger, refer the following table:
Larger side of the rectangle air pipe (mm) 500 630-1000 1250
Distance between the support and the hanger (mm) 3 2.5 2