Water Flow Vs Pressure Drop
Ceiling Exposed Split Type
Note :
a. PRESSURE DROP CORRECTION FACTOR = 1.2947 - 0.0021 * ( EWT°C * 1.8 + 32 )
b. PRESSURE DROP CORRECTION FACTOR = 1.2947 - 0.0021 * EWT°F
LITRES/M USGPM kPa PSI
3.29 0.87 4.21 0.61
4.39 1.16 5.94 0.86
5.49 1.45 7.84 1.14
6.59 1.74 9.90 1.44
7.69 2.03 12.12 1.76
4.29 1.13 6.84 0.99
5.72 1.51 10.20 1.48
7.15 1.89 13.71 1.99
8.58 2.27 17.38 2.52
10.01 2.64 21.21 3.08
5.29 1.40 1.77 0.26
7.06 1.86 2.84 0.41
8.82 2.33 4.08 0.59
10.58 2.80 5.48 0.80
12.35 3.26 7.06 1.02
7.79 2.06 11.73 1.70
10.38 2.74 16.90 2.45
12.98 3.43 22.70 3.29
15.58 4.11 29.13 4.22
18.17 4.80 36.19 5.25
10.20 2.69 23.78 3.45
13.60 3.59 31.82 4.62
17.00 4.49 39.92 5.79
20.40 5.39 48.09 6.97
23.80 6.29 56.31 8.17
10.61 2.80 27.78 4.03
14.14 3.74 37.56 5.45
17.68 4.67 47.59 6.90
21.22 5.60 57.87 8.39
24.75 6.54 68.41 9.92
FLOW RATE WATER PRESSURE DROP
MCM015EW
MCM020EW
MCM025EW
MCM010CBW
MCM015CBW
MODELS
MCM007CBW