46
Water Flow Vs Pressure Drop
Ceiling Cassette Split Type
Note :
a. PRESSURE DROP CORRECTION FACTOR = 1.2947 - 0.0021 * ( EWT°C * 1.8 + 32 )
b. PRESSURE DROP CORRECTION FACTOR = 1.2947 - 0.0021 * EWT°F
LITRES/M USGPM kPa PSI
11.40 3.01 8.80 1.28
15.20 4.02 14.19 2.06
19.00 5.02 20.60 2.99
22.80 6.02 27.99 4.06
26.60 7.03 36.30 5.26
12.90 3.41 10.91 1.58
17.20 4.54 17.61 2.55
21.50 5.68 25.60 3.71
25.80 6.82 34.81 5.05
30.10 7.95 45.15 6.55
15.14 4.00 18.53 2.69
20.18 5.33 28.86 4.19
25.23 6.67 39.90 5.79
30.28 8.00 51.65 7.49
35.32 9.33 64.11 9.30
17.11 4.52 22.97 3.33
22.82 6.03 35.27 5.11
28.52 7.53 48.49 7.03
34.22 9.04 62.63 9.08
39.93 10.55 77.70 11.27
18.58 4.91 30.11 4.37
24.78 6.55 45.92 6.66
30.97 8.18 63.00 9.14
37.16 9.82 81.35 11.80
43.36 11.45 100.98 14.65
MCK025AW
MCK030AW
MCK040AW
MCK050AW
FLOW RATE WATER PRESSURE DROP
MODELS
MCK020AW