MCQUAY Service Guide Book     Diagnosis
 
   
50 
   
 Chilled Water Fan Coil Unit 
 
Model Board Handset 
MWM 05 – 25FW, 301W  W1V3  G7 / SLM3 / Netware 3 / SLM8 
MCK 20 – 50AW/MWH  W1V3  G7 / SLM3 / Netware 3 / SLM8 
MCK 15 – 25BW  W1V3  G7 / SLM3 / Netware 3 / SLM8 
MCK 10 – 20CW  W1V3  G7 / SLM3 / Netware 3 / SLM8 
MCM 20 – 50DW/CBW  W1V3  G7 / SLM3 / Netware 3 / SLM8 
MCC 10 – 60CW  W1V3  SLM3 / Netware 3 / SLM8 
MDB 75 – 150BW  N/A  No Controller  
 
Self Diagnostic Table – W1V3 
Fault Indication 
POWER LED 
/ COOL LED 
Other LEDs 
Error 
Code 
Action 
Room sensor missing  Blinks 4 times  FAN blinks  E1   Check room sensor 
connection / change room 
sensor  
Indoor coil sensor missing  Blinks 4 times  SLEEP blinks  E2   Check indoor coil sensor 
connection / change indoor 
coil sensor 
Pump fault  Blinks 2 times  COOL & FAN 
blink 
E6   Clear the clogging at drain 
pipe. If pump is not working, 
change the pump 
Pipe water temperature 
poor 
Blinks 3 times  COOL & DRY 
blink 
E4  
- 
Pipe water temperature 
fault 
Blinks 1 time  COOL blinks  E5  
- 
 
 
Model Board Handset 
MWM 07 – 25G2W  W2  G17 / SLM3 / Netware 3 / SLM8 
MWM 301W  W2  G17 / SLM3 / Netware 3 / SLM8 
MCK 20 – 50AW/MWH  W2  G17 / SLM3 / Netware 3 / SLM8 
MCK 15 – 25BW  W2  G17 / SLM3 / Netware 3 / SLM8 
MCK 10 – 20CW  W2  G17 / SLM3 / Netware 3 / SLM8 
MCM 07 – 15CBW  W2  G17 / SLM3 / Netware 3 / SLM8 
MCM 20 – 50DW  W2  G17 / SLM3 / Netware 3 / SLM8 
MCM 15 – 25EW  W2  G17 / SLM3 / Netware 3 / SLM8 
MCC 10 – 60CW  W2  SLM3 / Netware 3 / SLM8 
MDB 75 – 150BW  N/A  No Controller  
 
 
Self Diagnostic Table – W2 
Fault Indication  COOL LED 
Error 
Code 
Action 
Room sensor error (short/open)  Blink 1 time  E1  Check room sensor 
connection / change room air 
sensor  
Pipe water sensor error (short/open)  Blink 2 times  E2  Check pipe water sensor 
connection / change pipe 
water sensor 
Water pump error  Blink 6 times  E6  Clear the clogging at drain 
pipe. If pump is not working, 
change the pump 
Pipe water temperature fault  Blink 5 times  E5   
Window open activated*  Blink 3 times  -  - 
Antifreeze mode activated*  Blink 7 times  -  - 
Load shedding activated*  Blink 8 times  -  - 
*Applicable for 4 pipes applications only.