MCQUAY Service Guide Book     Diagnosis
 
   
49 
   
 Ceiling Exposed D / E Series Model 
 
Model Board Handset 
MCM 20/25/30/40/50D/DR  L208A  G17 / SLM3 / Netware 3 / SLM8 
MCM 15/20/25/28E/ER  L208A  G17 / SLM3 / Netware 3 / SLM8 
 
 
COOL 
 
 
(Green) 
DRY 
 
 
(Orange) 
FAN 
 
 
(Green) 
HEAT 
 
 
(Red) 
Error Code
(SLM3 / 
Netware 3) 
Operation / Faulty 
Indication 
Action 
  
- Cooling mode  - 
  
- Dry mode  - 
  
- Fan mode  - 
  
- Heating mode  - 
  
- 
Auto mode in 
cooling operation 
- 
  
- 
Auto mode in 
heating operation 
- 
  
E1 
Room air sensor 
contact loose / short 
Check room sensor 
connection / change room  
sensor  
  
E2 
Indoor coil sensor 
contact open  
Check indoor coil sensor 
connection / change indoor 
coil sensor  
  
E3 
Outdoor coil sensor 
contact open  
Check outdoor coil sensor 
connection / change 
outdoor coil sensor 
  
E4 
Compressor 
overload protection / 
Indoor coil sensor 
short / Outdoor coil 
sensor short 
If running ampere highly 
increase, change the 
compressor. If not, replace 
the coil sensor 
  
E5 Gas leak 
Check for leakage & repair 
/ Top up refrigerant   
  
E7 
Outdoor coil sensor 
exist (MS model) 
Remove outdoor coil 
sensor 
  
E8 
Hardware error (tact 
switch pin short) 
 
Replace the tact switch 
control board 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
ON  ON or OFF  BLINKING
 
Blink Heat, Cool, follow by Fan, Dry