7.5 General Troubleshooting Guide 
 
By means of pressure readings: 
 
Pressure Probable Cause 
 
Too Low 
A Little Low 
Normal 
A Little 
High 
Too High 
 
High Side 
Low Side 
 1. Overcharged with refrigerant. 
2. Non-condensable gases in refrigerant 
circuit (eg. Oil) 
3. Obstructed air-intake / discharge. 
4. Short circuit of hot air at condensing unit. 
High Side 
Low Side 
          1. Poor compression / no compression 
(compressor defective). 
2. Check valve stick in open position. 
3. Reversing valve leaking (for heatpump 
only). 
High Side 
Low Side 
 1. Undercharged with refrigerant. 
2. Refrigerant leakage. 
3. Air filter clogged / dirty (indoor unit). 
4. Indoor fan locked (cooling). 
5. Defective defrosts control, outdoor coil 
freeze up (heating). 
6. Outdoor fan locked (heating). 
High Side 
Low Side 
 1. Outdoor fan blocked (cooling). 
2. Outdoor coil dirty (cooling). 
3. Indoor fan locked (heating). 
4. Indoor filter clogged dirty (heating). 
High Side 
Low Side 
          1. Air intake temperature of indoor unit too 
high. 
 
Data 
Circuit