MCQUAY Service Guide Book     Diagnosis
 
   
52 
   
Water Source Split Unit – Ceiling Cassette A / B / C 
Series Model  
 
Model Board Handset 
M5CKWS 20/25/30/40/50AR   LWS2.0  G17 / SLM3 / Netware 3 / SLM8 
M5CKWS 10/15/20CR   LWS2.0  G17 / SLM3 / Netware 3 / SLM8 
 
 
POWER 
 
 
(Green) 
TIMER 
 
 
(Orange) 
HEAT 
 
 
(Red) 
Error Code 
(SLM3 / 
Netware 3) 
Operation / Faulty 
Indication 
Action 
 
  
- Cooling mode  - 
  
- Timer On  - 
  
- Heating mode  - 
  
- 
Auto mode in cooling 
operation 
- 
  
- 
Auto mode in heating 
operation 
- 
  
E1 
Room air sensor 
contact loose / short 
Check room sensor connection 
/ change room sensor  
  
E2 
Indoor coil sensor 
contact loose / open 
Check indoor coil sensor 
connection / change indoor coil 
sensor  
  
E3 
Outdoor coil sensor 
contact loose / open 
Check outdoor coil sensor 
connection / change outdoor 
coil sensor 
  
E4 
Compressor overload 
protection 
If running ampere highly 
increase, change the 
compressor 
  
E6 Pump fault 
Clear the clogging at drain 
pipe. If pump is not working, 
change the pump 
  
E5 Gas leak 
Check for leakage & repair / 
Top up refrigerant