(g) Unit Conversion
  In the case of converting standard unit to downfl ow unit, follow the steps as stated below:
5RT90/120/150/180BR
Step 1 Step 2
Step 4 Step 3
Remove the side panel
Remove the Pulley Belt
Detached the 
blower support
Detached blower
Remove screws 
at both sides
For 5RT90BR:
The two side plates are screwed 
on the blower support as shown 
For 5RT120/150/180BR:
The two downfl ow structure 
are screwed to blower
Cover the 
horizontal supply 
opening with the 
blower support that 
detached from the 
blower.
Turn the blower to face bottom.
Screw at both sides.
Install back 
the pulley 
belt. Adjust 
the belt 
tension by 
moving the 
motor base.
Cover the horizontal 
return opening with the 
cover and screw tightly
Unscrew the vertical 
return cover from the 
base panel
Remove the side 
panel at return side 
Lastly, install back the side panel.
Install back the pulley belt. Adjust the belt tension. 
Lastly, install back the side panel.
Note:
For down fl ow conversion, belt length will need to 
be changed.
For unit with standard pulley, belt length  = a mm
Shaft to shaft Distance for downfl ow, C-C  = b mm
5RT90BR 5RT120BR 5RT150BR 5RT180BR
a 1120 1180 1150 1362
b 380 410 380 460