28 IM708
Unit Options
Duct High Limit
A duct high limit (DHL) pressure control is provided as stan-
dard with all units having variable air volume control. The 
duct high limit is intended to protect the ductwork, etc. from 
over pressurization caused by tripped fire dampers or a con-
trol failure. When the duct pressure exceeds the setting of the 
control, the unit is de-energized via the MicroTech II con-
troller and an alarm condition indicated. After the reason for 
trip has been identified and corrected, the control can be 
reset via the MicroTech II keypad/display interface.
The duct high limit is factory installed including sensing tub-
ing, and preset for a 3.0"  wc trip point. The control can be 
readjusted in the field to match the specific ductwork of a 
project. The switch has a field adjustable set point range of 
0.17 to 5.0 inches of H2O. Turn adjustment screw clockwise 
to decrease differential pressure setting. Turn adjustment 
screw counterclockwise to increase differential pressure set-
ting. DHL is located in the fan section on the motor side.
Phase Fail/Under Voltage Protection
The monitor is a microprocessor controlled device which 
provides protection against three-phase electrical motor loss 
due to low voltage, phase loss, voltage unbalance and phase 
reversal. The microprocessor constantly monitors the three-
phase line voltages and detects these harmful power line 
conditions. Whenever any of these conditions occur, the 
SWP controls are deactivated and remain deactivated until 
power line conditions return to an acceptable level. Trip and 
reset delays have been provided to prevent nuisance tripping 
due to rapid power fluctuations. The trip and reset delays are 
field adjustable. The monitor also provides a variable line 
voltage adjustment.
Duct Static Pressure Sensor
All units provided with variable air volume control include a 
factory mounted static pressure sensor (SPS1). The unit can 
also have an optional second static pressure sensor, SPS2. 
The sensor is factory wired and requires field installation of 
1/4" I.D. sensor tubing to the selected duct location. 
Note:  Be sure that tubing complies with local code 
requirements. Flame retardant plastic or metal tub-
ing may be required. Carefully select the ductwork 
sensing point for the pressure sensor. Improper 
location of the sensing point will result in unsatis-
factory operation of the entire variable air volume 
system. The following guidelines should be adhered 
to:
1. Sense near the end of long duct runs to ensure that all 
terminal box take-offs along the run will have adequate 
static pressure to operate.
2. The end of the sensing tube must be perpendicular to the 
airflow in order to sense only static pressure.
3. The sensing tube should be located in a nonturbulent 
flow area of the duct. Keep several duct widths away 
from take-off points, bends or neck downs.
Mounting instructions (See Figure 28)
1. Drill hole in duct at remote sensing point and install a 
rubber grommet. Insert sensing tube 1/8" into the duct 
and securely clamp tubing to the duct, being sure not to 
stress or kink the tubing. The end of the sensing tube 
must be smooth and cut straight across. An angle cut 
will affect operation.
2. Clamp a second tube to the outside of the duct at the 
location of the sensing point.
3. Run both tubes along the ductwork and back to the unit. 
The tubing may be routed to the pressure sensor (SPS1) 
by drilling two holes through the unit upright post. A 
grommet must be used at each hole to protect the tubing 
and seal the cabinet.
Note: To avoid confusion between "high" and "low" tubing, 
it is recommended that two different tubing colors be 
used and that this information be recorded, along with 
the sensing point location, on the master building blue-
prints.
4. Connect tubing to the high and low ports on the sensor.
Figure 28
Building Static Pressure Sensor
If a unit has direct building static pressure control capability, 
static pressure taps must be field installed and connected to 
pressure sensor SPS1 in the unit. This sensor is located on 
the control panel.
The two static pressure sensing taps must be carefully 
located and installed. Improper location or installation of the 
sensing taps will cause unsatisfactory operation. Following 
are pressure tap location and installation recommendations 
for both building envelope and lab, or "space within a 
space," pressure control applications. The installation must 
comply with local code requirements.