IM708 39
Check, Test and Start Procedure Form
Check, Test and Start Procedure for SWP/SWT (Self-contained Air Conditioning Systems)
Job Name: McQuay G.O. No.:
Installation Address:
City: State:
Purchasing Contractor:
City: State:
Unit Model No.: Serial No.:
Compressor No. 1 Serial No.
Compressor No. 2 Serial No.
Compressor No. 3 Serial No. Compressor No. 4 Serial No.
Compressor No. 5 Serial No. Compressor No. 6 Serial No.
Mark N/A on all items not applying to the type of the unit. See IM Bulletin for more information. Any additional comments
may be made on a separate sheet of paper and attached to this form.
INITIAL CHECK
A. Is any shipping damage visible? Yes No
B. Is unit installed level? Yes No
C. Is unit positioned to provide adequate free area for service and operation? Yes No
D. Are fan drives properly aligned and belts adjusted? Yes No
E. Does fan turn freely? Yes No
F. Tightened all setscrews on pulleys, bearings and fans? Yes No
G. Have the Condenser Water Temperature Sensors been located correctly? Yes No
H. Has the Installing Contractor installed the Return Air Temperature Sensor
in the Return Air stream? Yes No
I Has the Installing Contractor installed the high & low Static Pressure Sensor
tubing in the ductwork? Yes No
J. Does electrical service correspond to unit nameplate? Yes No
K. Adequate disconnect and circuit protectors installed? Yes No
L. Is the unit adequately grounded? Yes No
M. Are all electrical power connections tight? Yes No
N. Have the compressor heaters operated continuously for 24 hours prior to start up? Yes No
O. Does all electrical wiring conform to unit electrical diagram? Yes No
P. Does all field wiring conform to electrical diagrams? Yes No
Q . Are all service valves open? Yes No
R. Have all the shipping hold-down plates securing the fan frame been removed? Yes No
S. Unit with ducted return, has the low side tubing for PC5 (dirty filter switch) been
Installed? Yes No
T. Are all the cleanout plugs installed (condenser, condensate trap & optional
waterside economizer)? Yes No
Compressorized Equipment Warranty Registration Form:
This form must be filled out and returned to McQuay, Warranty
Department, within 10 days in order to comply with the terms of
McQuay Warranty.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay SWP 095 and is the answer not in the manual?

McQuay SWP 095 Specifications

General IconGeneral
BrandMcQuay
ModelSWP 095
CategoryAir Conditioner
LanguageEnglish

Related product manuals