22
4. Disconnect the charge hose from the vacuum pump.
Vacuum pump oil, if the vacuum pump oil becomes dirty or depleted, replenish as
needle.
5.3.8 Gas charging
Procedure:
1. Connect the charge hose to the charging cylinder.
Connect the charge hose which you disconnected from the vacuum pump to the
valve at the bottom of the cylinder.If the refrigerant is R410A, make the cylinder bottom up
to ensure liquid charge.
2. Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge
set to purge the air (be careful of the liquid refrigerant).
3. Open the valves (Low side) on the charge set and charge the system with liquid