Installation Manual
TypeDR Family with Class IISeriesDR-15, DR-30, DR-60, DR-100
DR-15-5 INPUT: 100 -240VAC 0.88A 50/60Hz OUTPUT: 5V 2.4A
DR-15-12 INPUT: 100 -240VAC 0.88A 50/60Hz OUTPUT: 12V 1.25A
DR-15-15 INPUT: 100 -240VAC 0.88A 50/60Hz OUTPUT: 15V 1A
DR-15-24 INPUT: 100 -240VAC 0.88A 50/60Hz OUTPUT: 24V 0.63A
DR-30-5 INPUT: 100 -240VAC 1.1A 50/60Hz OUTPUT: 5V 3A
DR-30-12 INPUT: 100 -240VAC 1.1A 50/60Hz OUTPUT: 12V 2A
DR-30-15 INPUT: 100 -240VAC 1.1A 50/60Hz OUTPUT: 15V 2A
DR-30-24 INPUT: 100 -240VAC 1.1A 50/60Hz OUTPUT: 24V 1.5A
DR-60-5 INPUT: 100 -240VAC 1.8A 50/60Hz OUTPUT: 5V 6.5A
DR-60-12 INPUT: 100 -240VAC 1.8A 50/60Hz OUTPUT: 12V 4.5A
DR-60-15 INPUT: 100 -240VAC 1.8A 50/60Hz OUTPUT: 15V 4A
DR-60-24 INPUT: 100 -240VAC 1.8A 50/60Hz OUTPUT: 24V 2.5A
DR-100-12 INPUT: 100 -240VAC 3A 50/60Hz OUTPUT: 12V 7.5A
DR-100-15 INPUT: 100 -240VAC 3A 50/60Hz OUTPUT: 15V 6.5A
DR-100-24 INPUT: 100 -240VAC 3A 50/60Hz OUTPUT: 24V 4.2A
Introduction
DR with class II is a double insulated DIN rail power supply series, meaning it is ungrounded. Like other Mean Wells
DIN series, they can be mounted on a TS35 Standard DIN rail.
Installation
1Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit
in use to prevent it from overheating. Also a 10-15 cm clearance must be kept when the adjacent device is a
heat source.
2The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom and output on
the top for DR-15, the input terminals on the right and output on the left for DR-30, DR-60, and DR-100.
Mounting orientations other than that, such as upside down, horizontal, or table-top mounting, is not
allowed.
3Use stranded copper wire only, and recommended wires are shown as below.
AWG
18
16
14
12
Rated Current of
Equipment (Amp)
6A
6-10A
13-16A
16-25A
Cross-section of
Lead(mm
2
)
0.75
1.00
1.5
2.5
NoteCurrent each wire carries should be de-rated to 80% of the current suggested
above when using 5 or more wires connected to the unit.
Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are
securely fixed to prevent poor contact. If the power supply possesses multi-output terminals, please make
sure each contact is connected to wires to prevent too much current stress on a single contact.