Do you have a question about the Mean Well DR-15-5 and is the answer not in the manual?
Ensure adequate clearance (5mm L/R, 40mm top, 20mm bottom) to prevent overheating.
Vertical mounting with input terminals down is recommended for optimal cooling.
Use stranded copper wire, observe AWG ratings and derate for multiple connections.
Use wire rated for at least 80°C, such as UL1007.
Recommended wire strapping length is 7mm/0.275inch.
Recommended torque setting for terminals is 5 kgf-cm (4.4 Lb-in).
Recommended screwdriver is 3mm, slotted type.
Suggested fuse type and maximum number of DR Class II PSUs for 230V circuit breakers.
Detailed steps for tilting, fitting, sliding, locking, and checking DIN rail mount.
Risk of electrical shock; examination by qualified technician is required for failures.
Protect openings from foreign objects/liquids to prevent fire and short circuits.
Respect operating temperature limits (50°C for DR-15/30, 40°C for DR-60/100).
Disconnect system from supply voltage before installation, maintenance, or modification.
Replace fuses only with the same type and rating for continued fire protection.
Information on marking for restricted use of hazardous substances in electronics.
Details on lead, mercury, cadmium, chromium, PBB, and PBDE content in product parts.