TypeNDR DIN rail power supplySeriesNDR-75, 120, 240, 480
NDR-75-12 INPUT: 100-240VAC 1.6A 50/60Hz OUTPUT: 12V 6.3A
NDR-75-24 INPUT: 100-240VAC 1.6A 50/60Hz OUTPUT: 24V 3.2A
NDR-75-48 INPUT: 100-240VAC 1.6A 50/60Hz OUTPUT: 24V 1.6A
NDR-120-12 INPUT: 100-240VAC 2.6A 50/60Hz OUTPUT: 12V 10A
NDR-120-24 INPUT: 100-240VAC 2.6A 50/60Hz OUTPUT: 24V 5A
NDR-120-48 INPUT: 100-240VAC 2.6A 50/60Hz OUTPUT: 48V 2.5A
NDR-240-24 INPUT: 100-240VAC 2.8A 50/60Hz OUTPUT: 24V 10A
NDR-240-48 INPUT: 100-240VAC 2.8A 50/60Hz OUTPUT: 48V 5A
NDR-480-24 INPUT: 100-240VAC 5.3A 50/60Hz OUTPUT: 24V 20A
NDR-480-48 INPUT: 100-240VAC 5.3A 50/60Hz OUTPUT: 48V 10A
Introduction
NDR is a DIN rail power supply series with an economical price and slim design. Like other Mean Wells DIN series,
they can be mounted on a TS35 Standard DIN rail.
Installation
1Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit
in use to prevent it from overheating. Also a 10-15 cm clearance must be kept when the adjacent device is a
heat source.
2The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom and output on
the top. Mounting orientations other than that, such as upside down, horizontal, or table-top mounting, is not
allowed.
3Use copper wire only, and recommended wires are shown as below.
AWG
18
16
14
12
Rated Current of
Equipment (Amp)
7A
10A
15A
20A
Cross-section of
Lead(mm
2
)
0.8
1.3
2.1
3.3
Note: Current each wire carries should be de-rated to 80% of the current suggested
above when using 5 or more wires connected to the unit.
Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are
securely fixed to prevent poor contact. If the power supply possesses multi-output terminals, please make
sure each contact is connected to wires to prevent too much current stress on a single contact.
4Use wires that can withstand temperatures of at least 80°C, such as UL1007.
5Recommended wire strapping length is 5mm (0.197”).
6Recommended screwdriver is 3mm, slotted type.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mean Well NDR-240 Series and is the answer not in the manual?

Mean Well NDR-240 Series Specifications

General IconGeneral
ModelNDR-240 Series
Output Power240W
Output Voltage12V, 24V, 36V, 48V
Frequency47 ~ 63Hz
CoolingConvection
Output Current20A, 10A, 5A
Input Voltage90 ~ 264VAC, 127 ~ 370VDC
EfficiencyUp to 90%
Operating Temperature-30°C ~ +70°C
ProtectionsShort circuit, Overload, Over Voltage
Safety StandardsEN62368-1
EMC StandardsEN55032