File Name:DRC-100-SPEC 2024-01-26
Model Encoding
Universal AC input / Full range
Protections: Short circuit / Overload / Over voltage
Battery low / Battery reverse polarity protection protection
by fuse
Can be installed on DIN rail TS-35/7.5 or 15
Alarm signal for AC OK and Battery low (via relay)
Cooling by free air convection
LED indicator for power on
100% full load burn-in test
3 years warranty
Security system
Emergency lighting system
Alarm system
DC UPS system
Central monitoring system
Access systems
Features Applications
100W Single Output with Battery Charger (UPS Function)
DRC-100 series
Output wattage
Output voltage
Series name
ADRC - 100
Description
DRC-100 is a 96W AC/DC DIN rail type security power supply series. In addition to the primary output, there
is a charger output with a smaller rated current, enabling the backup power supply application the security
access systems require. DRC-100 accepts the universal input between 90VAC and 264VAC, and supplies
13.8VDC and 27.6VDC at output, respectively. With the efficiency up to 89%, it can operate with air convection
cooling under -30 through 70 . In addition to the key protection features such as overload protection, ℃℃
over voltage protection, battery low cut off, and battery reverse polarity protection (by fuse), the alarm
signal for AC OK and battery low signaling is provided, via relay contact output, to facilitate the system design.
AS/NZS60950-1
Bauar
Sicherheit
egel gema
t gepruft
od
be
www.
ID 2000000000
tuv.com
wac g
os
TPTC004BS EN/EN62368-1 IEC62368-1UL62368-1
https://www.meanwell.com/serviceGTIN.aspx
MW Search:
GTIN CODE
Question and Answer IconNeed help?

Do you have a question about the Mean Well DRC-100 Series and is the answer not in the manual?

Overview

The MEAN WELL DRC-100 series is a 96W AC/DC DIN rail type security power supply with a built-in battery charger (UPS function). This series is designed to provide a primary output along with a charger output, enabling backup power supply applications, particularly for security access systems.

Function Description:

The DRC-100 operates by accepting a universal input voltage ranging from 90VAC to 264VAC. It then supplies a regulated DC output, specifically 13.8VDC for the DRC-100A model and 27.6VDC for the DRC-100B model. In addition to the primary DC output, it features a charger output with a smaller rated current, which is crucial for maintaining a connected backup battery. When AC mains power is available, the unit simultaneously charges the battery and provides power to the load. In the event of an AC mains failure, the connected battery automatically takes over to supply power to the load, ensuring continuous operation (UPS function).

The device incorporates several key protection features to ensure reliable and safe operation. These include short circuit protection, overload protection, and over voltage protection for the outputs. For battery management, it provides battery low protection and battery reverse polarity protection, with the latter implemented via a fuse.

To facilitate system integration and monitoring, the DRC-100 series includes alarm signals for "AC OK" and "Battery Low." These signals are provided via relay contact outputs, allowing external systems to monitor the status of the AC input and the battery charge level. The "AC OK" signal indicates whether the AC mains power is present, while the "Battery Low" signal alerts when the battery voltage drops below a specified threshold.

The power supply is designed for efficient operation, with an efficiency of up to 89%. It utilizes free air convection for cooling, allowing it to operate across a wide ambient temperature range from -30°C to +70°C. An LED indicator is present to show the power-on status of the unit.

Important Technical Specifications:

  • Output Power: 96.6W (Rated Power)
  • Input Voltage Range: 90~264VAC (Universal AC input), 127~370VDC
  • Frequency Range: 47~63Hz
  • Efficiency (Typ.): 87% (DRC-100A), 89% (DRC-100B)
  • DC Output Voltage:
    • DRC-100A: CH1: 13.8V (4.5A), CH2: 13.8V (2.5A)
    • DRC-100B: CH1: 27.6V (2.25A), CH2: 27.6V (1.25A)
  • Voltage Adjustment Range:
    • DRC-100A: CH1: 12~15V
    • DRC-100B: CH1: 24~30V
  • Ripple & Noise (max.): 120mVp-p (DRC-100A), 240mVp-p (DRC-100B)
  • Setup, Rise Time: 2400ms, 50ms/230VAC (at full load)
  • Hold Up Time (Typ.): 50ms/230VAC
  • Overload Protection: 105~150% rated output power, hiccup mode, auto-recovery.
  • Over Voltage Protection:
    • DRC-100A: CH1: 14.49~18.63V
    • DRC-100B: CH1: 28.98~37.26V
    • Protection type: Shut down o/p voltage, re-power on to recover.
  • Battery Cut Off Voltage: 10±0.5V (DRC-100A), 20±1V (DRC-100B)
  • Alarm Signal (Relay Contact Output):
    • AC OK: ON (AC OK), OFF (AC Fail), max. rating: 30V/1A
    • Battery Low: OFF (Battery OK), ON (Battery Low), max. rating: 30V/1A
  • Working Temperature: -30~+70°C
  • Working Humidity: 20~90% RH non-condensing
  • Storage Temperature & Humidity: -40~+85°C, 10~95% RH
  • Vibration: 10~500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
  • Safety Standards: UL62368-1, TUV BS EN/EN62368-1, EAC TP TC 004, AS/NZS 60950.1 approved
  • Withstand Voltage: I/P-O/P:3KVAC, I/P-FG:2KVAC, O/P-FG:0.5KVAC
  • Isolation Resistance: I/P-O/P, I/P-FG, O/P-FG: 100M Ohms/500VDC / 25°C/70% RH
  • EMC Emission: Compliance to BS EN/EN55032 (CISPR32) Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020
  • EMC Immunity: Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61204-3, light industry level, EAC TP TC 020; meet BS EN/EN54-4 for fire detection and fire alarm systems
  • MTBF: 1820.4K hrs min. (Telcordia SR-332), 410.1K hrs min. (MIL-HDBK-217F)
  • Dimensions (WHD): 5590100mm
  • Weight: 0.37Kg

Usage Features:

  • DIN Rail Mountable: The DRC-100 series is designed for easy installation on DIN rails (TS-35/7.5 or TS-35/15), making it suitable for integration into industrial control cabinets and security systems.
  • Backup Power Capability: Its primary feature is the UPS function, which automatically switches to battery power during AC mains interruptions, ensuring uninterrupted operation of connected loads. This is particularly valuable for critical security and access control systems.
  • Alarm Signaling: The relay contact outputs for "AC OK" and "Battery Low" provide crucial status information to external monitoring systems, enabling proactive maintenance and system management. An external voltage source (max. 30V) and resistor are required for these alarm functions, with a maximum sink current of 1A.
  • Wide Operating Temperature: The ability to operate from -30°C to +70°C makes it suitable for use in various environments, including those with challenging temperature conditions.
  • Universal Input: The wide input voltage range (90-264VAC) allows for global compatibility and flexibility in power source connections.
  • Adjustable Output Voltage: The adjustable output voltage for CH1 provides flexibility to fine-tune the output to specific load requirements.
  • Cooling: Utilizes free air convection, eliminating the need for internal fans and reducing potential points of failure and noise.
  • LED Indicator: A simple LED indicator provides immediate visual confirmation of the power-on status.

Maintenance Features:

  • 100% Full Load Burn-in Test: Each unit undergoes a 100% full load burn-in test during manufacturing, ensuring high reliability and stability from the start.
  • Protection Features: Comprehensive protection mechanisms (short circuit, overload, over voltage, battery low, battery reverse polarity) minimize damage to the unit and connected equipment, reducing the need for frequent repairs.
  • Relay Contact Outputs for Alarms: The alarm signals simplify troubleshooting and maintenance by providing clear indications of AC power status and battery health, allowing for timely intervention.
  • 3-Year Warranty: MEAN WELL provides a 3-year warranty, reflecting confidence in the product's durability and reducing long-term maintenance concerns.
  • Installation Manual: Detailed installation instructions are available online, guiding users through proper setup and ensuring correct operation.
  • Component Design: The power supply is considered a component for integration into final equipment. Users are advised to re-confirm that the final equipment meets EMC directives. Installation clearances (40mm top, 20mm bottom, 5mm sides) are recommended for optimal cooling and performance.

Mean Well DRC-100 Series Specifications

General IconGeneral
BrandMean Well
ModelDRC-100 Series
CategoryPower Supply
LanguageEnglish

Related product manuals