Installation Manual
TypeEDR DIN rail power supplySeriesEDR-75, EDR-120, EDR-150
EDR-75-12 INPUT: 100-240VAC 1.6A 50/60Hz OUTPUT: 12V 6.3A
EDR-75-24 INPUT: 100-240VAC 1.6A 50/60Hz OUTPUT: 24V 3.2A
EDR-75-48 INPUT: 100-240VAC 1.6A 50/60Hz OUTPUT: 48V 1.6A
EDR-120-12 INPUT: 100-240VAC 2.6A 50/60Hz OUTPUT: 12V 10A
EDR-120-24 INPUT: 100-240VAC 2.6A 50/60Hz OUTPUT: 24V 5A
EDR-120-48 INPUT: 100-240VAC 2.6A 50/60Hz OUTPUT: 48V 2.5A
EDR-150-24 INPUT: 100-120VAC 2.6A 50/60Hz OUTPUT: 24V 5.2A
200-240VAC 1.65A 50/60Hz 24V 6.5A
Introduction
EDR is a DIN rail power supply series with an economical price and slim design. Like other Mean Well’s DIN series,
they can be mounted on a TS35 Standard DIN rail.
Installation
1Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit
in use to prevent it from overheating.
2The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom and output on
the top. Mounting orientations other than that, such as upside down, horizontal, or table-top mounting, is not
allowed.
3Use copper wire only, and recommended wires are shown as below.
AWG 18 16 14 12
Rated Current of
Equipment (Amp)
7A 10A 15A 20A
Cross-section of
Lead(mm
2
)
0.8 1.3 2.1 3.3
Note: Current each wire carries should be de-rated to 80% of the current suggested
above when using 5 or more wires connected to the unit.
Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are
securely fixed to prevent poor contact. If the power supply possesses multi-output terminals, please make
sure each contact is connected to wires to prevent too much current stress on a single contact.
4Use wires that can withstand temperatures of at least 80°C, such as UL1007.
5Recommended wire strapping length is 5mm (0.197”).
6Recommended screwdriver is 3mm, slotted type.
Question and Answer IconNeed help?

Do you have a question about the Mean Well EDR-75-12 and is the answer not in the manual?

Summary

Introduction

Installation

Ventilation and Mounting Requirements

Ensure proper ventilation clearances and vertical mounting orientation for optimal performance and safety.

Wire and Tool Specifications

Details on using copper wire, temperature ratings, strapping length, and recommended screwdriver.

Additional Installation Details

Terminal Torque and Fuse Recommendations

Recommended torque settings for terminals and suggested fuse/circuit breaker ratings for various models.

Mounting Instructions

Step-by-step guide for mounting the unit onto a DIN rail, ensuring secure locking.

Warning and Cautionary Notes

Electrical Safety Precautions

Highlights risks of electric shock, arc, and advises professional examination for failures.

Operational Safety

Covers burn hazards, fire risks, pollution degree, moisture, ambient temperature limits, and earth connection.

System Connection and Maintenance

Output Limits and Disconnection Procedure

Ensure output specifications are not exceeded and disconnect power before any work.

Fuse Replacement and Environmental Notes

Use identical fuses for fire protection and understand pollution degree definitions.

Manufacturer and Branch Office Information

Environmental Compliance Declarations

China RoHS Conformity

Declaration of conformity to China RoHS administrative measures for hazardous substances.

Environment Friendly Use Period Label

Information regarding the use period label for electronic products based on relevant standards.

China VOC Conformity

PBT TSCA Conformity

Five PBT Chemicals Declaration

Confirmation of compliance with TSCA section 6(h) for five PBT chemicals.

Mean Well EDR-75-12 Specifications

General IconGeneral
Input Voltage Range90 ~ 264 VAC
Input Frequency Range47 ~ 63 Hz
Output Voltage12V
Output Current6.25 A
Output Power75 W
EfficiencyUp to 88%
MountingDIN Rail
Cooling MethodFree Air Convection
ProtectionsShort Circuit, Overload, Over Voltage