DC4xD MK3 GENSET CONTROLLER USER MANUAL
7
Under speed
Low oil pressure
High water temperature
High Oil temperature
High Cylinder Temperature
High Tank temperature
Low fuel level
Low oil level
External instant unloading shutdown
External emergency alarm
RPM Lost
Sensor Open
Over Frequency
Under Frequency
Over voltage
Under voltage
Over current
Non-balance of current
Over power
Maintenance expire
Low water level alarm
Emergency Stop
Crank failure
Battery over voltage
Battery under voltage
The charger fails to charge
Charger charging failure
Stop Failure
5.Parameters
Options
Parameters
Working voltage
DC8V---36V Continuous
Power consumption
Standby24VMAX 1W
Working24VMAX 5W
AC Voltage Input
1P2W 30VAC-300VAC (ph-N)
2P3W 30VAC-300VAC (ph-N)
3P4W 30VAC-300VAC (ph-N)
Rotate speed sensor
Frequency
50-9000Hz
MAX Accumulating Time
99999.9HoursMin Store time:6min
Fuel Relay Output
Max 5Amp DC+VE Supply voltage
Start Relay Output
Max 5Amp DC+VE Supply voltage
AUX. OUTPUT1
Max 5Amp DC+VE Supply voltage
AUX. OUTPUT2
5AMP Non-contact normal open&normal close output
AUX. OUTPUT3
5AMP Non-contact normal open output