EasyManuals Logo

Mebay DC5 D MK3 Series User Manual

Mebay DC5 D MK3 Series
43 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #43 background imageLoading...
Page #43 background image
DC5xD MK3 GENSET CONTROLLER USER MANUAL
42
Unit operation but ATS
does not switch
Check the ATS.
Check the cable between the controller and the ATS.
USB communication is
abnormal
Check the USB connection.
Check whether the USB port of the computer is normal.
Check whether the USB driver is installed.
RS485 cannot
communicate normally
Check the connection.
Check if the communication ID number setting is correct.
Check if the A and B lines of RS485 are reversed.
Check if the RS485 communication line driver is installed or not.
Check if the communication port of the PC is damaged.
Add a 120 Ω resistor between the AB of the controller RS485.