Setting System Parameters
Certain facilities that can be set up by the service provider at commissioning. They are as follows:
Non-latching Zone
To enable this facility gain access to the service area of the panel and push the Non-latching zone
switch down (Fig.2). Then press the SYSTEM RESET switch. The panel will reset and the
non-latching zone feature will be available on zone 1.
Coincidence Detection
To enable this facility gain access to the service area of the panel. On the bit-switch (see Fig.2) move
switch 4 to the ON position. Then press the SYSTEM RESET button. The panel will reset and the
coincidence detection feature will then be available for use on zone 2.
Alarm Line Delays
Again, to enable alarm line delays gain access to the service area. The delay period is set by
adjusting the positions of the bit switches (see Fig.2) as follows:
SWITCH POSITION
123
DELAY
(MINS)
0OFFOFFOFF
1ON OFFOFF
2OFFON OFF
3ON ONOFF
4OFFOFFON
5ON OFFON
6OFFON ON
7ON ONON
After the delay period is selected press the SYSTEM RESET switch. The panel will reset, the ALARM
LINE DELAY indicator will light and the delays will be used when appropriate.
PAGE 24