Mounting | Wall |
---|---|
Detection Angle | 110° |
Operating Voltage | 230V AC |
Type | Passive Infrared Sensor |
Range | 12 meters |
Warns that installation must be done by qualified electricians.
Warns about water damage if not installed correctly and advises orientation.
Details how to feed the connection cable from behind or below.
Advises using a 16 A automatic circuit-breaker for fusing the ARGUS.
Details stripping cable and connecting conductors to terminals L, N, and earth.
Explains spikes with inductive loads and the use of a capacitor.
Attaching the upper section to the connection box using screws.
Instructs to connect the supply voltage for initial operation.
Adjusting ambient brightness level for movement detection triggering.
Configuring how long loads remain switched on after detection.