20
Technical data
Fluorescent lamps
AC 230 V: max. 1200 W, uncompensated
Capacitive load: max. 35 µF
Power consumption: < 1 W
Connecting terminals: for 2 x1.5 mm
2
or 2 x 2.5 mm
2
rigid
conductor, stripped length 14 mm
External diameter of a
cable: max. 14.5 mm
Area of detection: 110° (Argus 110) / 220° (Argus 220)
Range: max. 12 m
Number of levels: 7
Number of zones: ARGUS 110: 92 zones with
368 switching segments
ARGUS 220: 112 zones with
448 switching segments
Minimum mounting
height:
1.7 m
Recommended mounting
height:
2.5 m
Light sensor: infinitely adjustable externally
approx. 3–1000 lux
Switching duration: can be set externally at 6 levels
approx. 1 s – approx. 8 min
Possible settings for sensor
head
Wall mounting: 9° up, 24° down, 12° left/right, ± 12° axial
Ceiling mounting: 4° up, 29° down, 25° left/right, ± 8.5° axial
Type of protection: IP 55 at an angle of inclination from 15° to
90°
EC guidelines: Low-voltage guideline 73/23/EEC and
EMC guideline 89/336/EEC