66 UNT Controller—Unitary Controller (UNT)
grdloop
UNT
15 VDC
DVM < 5 VDC/VAC = OK (Isolated)
DVM > 5 VDC/VAC = Earth Grounded
100k ohm
1/4-watt
DVM
Field Wiring*
*AICOM, BICOM, ZBUS COM, AOCOM, BOCOM
24 VAC
24 VAC
24 VAC COM
Line
Voltage
Figure 37: Testing for Ground Loops
Connect the DVM across the 24 VAC and the 24 VAC common
terminal of the UNT. Read the voltage with all typical loads
energized.
A reading of 24 VAC is required when the line voltage is nominal.
If you read a value less than 20 VAC, make sure the primary voltage
matches the transformer’s voltage rating. For details, refer to the
Power Source and Loads section of this technical bulletin and
recalculate the VA requirements for the UNT.
You have completed the UNT isolation tests. If you plan to connect this
UNT to the N2 Bus for communication to other devices, refer to the
Application Specific Controllers Technical Manual (FAN 636.3), the
Introduction tab, the ASC and N2 Bus Networking and Troubleshooting
Guide Technical Bulletin (LIT-6363003).