72-1 PROFINET: bus error Communication is not possible, e.g. because the
bus cable has been disconnected. Check the
wiring and restart the PROFINET
communication.
72-2 PROFINET: range
overflow
Mathematical error during the conversion of
physical units.
Adapt the parameterisation.
72-3 PROFINET: invalid IP
configuration
Check whether the IP address, subnet mask and
gateway address are valid or permissible.
Change the IP configuration.
72-4 PROFINET: invalid
device name
Use a valid PROFINET device name (Name of
Station).
72-5 PROFINET: defective
module
Replace the PROFINET module.
72-6 PROFINET: invalid /
unsupported indication
The PROFINET feature that has been used is not
supported by the module.
Please contact the Technical Support team.
72-7 PROFINET: different
module configuration
Master/Slave
Check whether the telegram lengths set in the
PROFINET telegram editor match the setting in
the master.
72-8 PROFINET: failure in
cyclic data
Check wiring.
72-9 PROFINET:
communication error
Check the telegram configuration in the master.
Group 73: PROFINET
73-0 PROFIenergy: state not
possible
Request the PROFIenergy state again when the
motor is stopped.
73-1 PROFINET: wrong
firmware found
Please contact the Technical Support team.
Group 78: NRT communication
78-0 NRT: frame send error In general, no measure is required.
It may be helpful to reduce the bus load, e.g. by
reducing the number of devices connected to a
branch.
Group 79: RS232 communication
79-0 RS232 communication Please contact the Technical Support team.
Group 80: IRQ_0_3
80-0 Time overflow current
control IRQ
Select longer cycle times for the current, speed
and position controllers or interpolator.
Please contact the Technical Support team.
80-1 Time overflow speed
control IRQ
80-2 Time overflow position
control IRQ
80-3 Time overflow
interpolator IRQ