P341/EN AD/F43 Update Documentation
(AD) -16
MiCOM P341
Input 1 Trigger: No Trigger/Trigger/LH (Low to
High)/Trigger H/L (High to Low)
(up to):
Input 32 Trigger: No Trigger/Trigger
L/H/Trigger H/L
Measured Operating Data
(Measure’t Setup)
Default Display:
Access Level
3Ph + N Current
3Ph Voltage
Power
Date and Time
Description
Plant Reference
Frequency
Local Values: Primary/Secondary
Remote Values: Primary/Secondary
Measurement Ref: VA/VB/VC/IA/IB/IC
Measurement Mode: 0/1/2/3
Fix Dem Period: 1…99mins
Roll Sub Period: 1…99mins
Num Sub Periods: 1…15
Remote2 Values: Primary/Secondary
Communications
RP1 Address: (Courier or IEC870-5-103):
0…255
RP1 Address: (DNP3.0):
0…65534
RP1 Address: (MODBUS):
1…247
RP1 InactivTimer: 1…30mins
RP1 Baud Rate: (IEC870-5-103):
9600/19200 bits/s
RP1 Baud Rate: (MODBUS, Courier):
9600/19200/38400 bits/s
RP1 Baud Rate: (DNP3.0):
1200/2400/4800/9600/19200/ 38400 bits/s
RP1 Parity: Odd/Even/None
(MODBUS, DNP3.0)
RP1 Meas Period: 1…60s
(IEC870-5-103)
RP1 PhysicalLink:
Copper (EIA(RS)485/K bus) or Fiber Optic
RP1 Time Sync: Disabled/Enabled
MODBUS IEC Timer: Standard/Reverse
RP1 CS103Blocking:
Disabled
Monitor Blocking
Command Blocking
RP1 Port Config: (Courier):
K Bus
EIA485 (RS485)
RP1 Comms Mode: (Courier):
IEC60870 FT1.2
IEC60870 10-Bit No parity
Note: If RP1 Port Config is K Bus the baud
rate is fixed at 64 kbits/s
Optional Ethernet Port
NIC Tunl Timeout: 1...30mins
NIC Link Report: Alarm, Event, None
NIC Link Timeout: 0.1...60s
Optional Additional Second Rear
Communication
(Rear Port2 (RP2))
RP2 Port Config:
EIA(RS)232
EIA(RS)485
K-Bus
RP2 Comms Mode:
IEC60870 FT1.2
IEC60870 10-Bit No parity
RP2 Address: 0…255
RP2 InactivTimer: 1…30mins
RP2 Baud Rate:
9600/19200/38400 bits/s
Note: If RP2 Port Config is K Bus the baud
rate is fixed at 64 kbits/s
Commission Tests
Monitor Bit 1:
(up to):
Monitor Bit 8:
Binary function link strings, selecting which
DDB signals have their status visible in the
Commissioning menu, for test purposes
Test Mode:
Disabled
Test Mode
Blocked Contacts
Test Pattern:
Configuration of which output contacts are to
be energized when the contact test is
applied
Circuit Breaker Condition
Monitoring
(CB Monitor Setup)
Broken I^: 1.0…2.0
I^ Maintenance: Alarm Disabled/Enabled
I^ Maintenance: 1…25000
I^ Lockout: Alarm Disabled/Enabled
I^ Lockout: 1…25000
No. CB Ops Maint: Alarm Disabled/Enabled
No. CB Ops Maint: 1…10000
No. CB Ops Lock: Alarm Disabled/Enabled
No. CB Ops Lock: 1…10000
CB Time Maint: Alarm Disabled/Enabled
CB Time Maint: 0.005…0.500s
CB Time Lockout: Alarm Disabled/Enabled
CB Time Lockout: 0.005…0.500s
Fault Freq Lock: Alarm Disabled/Enabled
Fault Freq Count: 1…9999
Fault Freq Time: 0…9999s