IBEX 8 Nozzle SMALL FRAME_June 2020 June 20 Page 27 of 41
For more detailed descriptions reference WEG manual.
F0072
Motor overload fault (60 s in 1.5xlnom)
P0156, P0157, P0158 setting is too
low in relation to the motor operating
current.
Overload on the motor shaft
F0074
Ground overcurrent fault.
Note: This failure may be disabled by setting
P0343 = 0
Short-circuit to the ground in one or
more output phases.
Motor cable capacitance too high,
causing current peaks in the output.
F0076
This fault indicates the motor presents phase loss,
imbalanced phase current or is disconnected.
Motor wiring or connection error.
Loss of moto connection with the drive
or broken wire.
F0078
Overtemperature fault measured on
the motor
temperature sensor (Triple PTC) via analog input
Alx or digital input Dlx
Overload on the motor shaft.
Load cycle is too high (high number of
starts and stops per minute).
High ambient temperature around the
motor.
Poor contact or short-circuit
(3k9<RPTC<0K1).
Motor thermistor not installed.
Motor shaft in stuck.