IBEX 8 Nozzle SMALL FRAME_June 2020 June 20 Page 26 of 41
VARIABLE FREQUENCY DRIVE (VFD) FAULT CODES
DISPLAY
Undervoltage fault on the intermediate circuit.
• Wrong voltage supply; check if the
data on the inverter label complies
with the power supply and parameter
PO296.
• Supply voltage too low, producing
voltage on the DC link below the
minimum value (in P0004):
Ud<200 Vdc in 200-240 Vac (P0296=0).
Ud<360 Vdc in 380-480 Vac (P0296=1).
Ud<500 Vdc in 500-600 Vac (P0296=2).
• Phase fault in the input.
• Fault in the pre-charge circuit.
Overvoltage fault on the intermediate circuit.
• Wrong voltage supply; check if the
data on the inverter label complies
with the power supply and parameter
P0296.
• Supply voltage is too high, producing
voltage on the DC link above the
maximum value (in P0004):
Ud>410 Vdc in 200-240 Vac (P0296=0).
Ud>810 Vdc in 380-480 Vac (P0296=1).
Ud>1000 Vdc in 500-600 Vac (P0296=2).
• Load inertia is too high or deceleration
ramp is too fast.
• P0151 or P0153 setting is too high.
• Communication card failure
Overload fault on the power pack with IGBTs
(3 s in 1.5XL).
• Inverter output overcurrent (>2xl)
• Possible Cooling Fan Failure
Overcurrent or short-circuit on the output, DC link
or braking resistor.
• Short-circuit between two motor
phases.
• Short-circuit of the rheostatic braking
resistor connecting cables.
• IGBTs module in short-
damaged
• Start with too short acceleration ramp.
• Start with motor spinning without the
Flying Start function.