Midea AC Fan Coil Unit
20
(Continued)
MKH2(3)-700-R3
EWT
ΔT
Indoor
temp
(W.B.)
Indoor temperature (D.B.)
21
23
25
27
29
TC
SC
WF
WPD
TC
SC
WF
WPD
TC
SC
WF
WPD
TC
SC
WF
WPD
TC
SC
WF
WPD
°C
°C
°C
kW
kW
m^3/h
kPa
kW
kW
m^3/h
kPa
kW
kW
m^3/h
kPa
kW
kW
m^3/h
kPa
kW
kW
m^3/h
kPa
11
3
15
2.31
2.31
0.66
17.79
2.9
2.9
0.83
26.26
3.49
3.49
1
36.08
4.06
4.06
1.17
47.06
4.64
4.64
1.33
59.2
17
2.87
2.25
0.82
25.74
3.09
2.88
0.89
29.63
3.49
3.49
1
36.17
4.07
4.07
1.17
47.19
4.64
4.64
1.34
59.35
19
4.79
2.3
1.39
63.44
4.75
2.88
1.37
61.62
4.73
3.47
1.38
62.53
4.72
4.05
1.35
60.44
4.87
4.63
1.41
65.43
20
-
-
-
-
5.75
2.9
1.67
87.33
5.71
3.48
1.66
86.35
5.67
4.05
1.65
85.38
5.63
4.61
1.64
84.29
4
15
2.05
2.05
0.44
8.82
2.66
2.66
0.57
13.75
3.27
3.27
0.71
19.68
3.85
3.85
0.83
26.13
4.43
4.43
0.96
33.23
17
2.29
1.99
0.49
10.62
2.72
2.65
0.59
14.28
3.27
3.26
0.71
19.69
3.86
3.86
0.83
26.2
4.43
4.43
0.96
33.32
19
4.08
2.03
0.88
28.87
4.05
2.61
0.88
28.49
4.06
3.2
0.88
28.51
4.23
3.81
0.92
30.68
4.53
4.42
0.98
34.31
20
-
-
-
-
5.06
2.63
1.09
41.49
5.03
3.22
1.08
41.03
4.99
3.79
1.08
40.49
5.06
4.38
1.09
41.55
5
15
1.73
1.73
0.3
4.54
2.4
2.4
0.41
7.89
3.02
3.02
0.52
11.67
3.62
3.62
0.63
15.9
4.2
4.2
0.73
20.57
17
1.79
1.71
0.31
4.82
2.4
2.4
0.42
7.93
3.02
3.02
0.52
11.7
3.62
3.62
0.63
15.94
4.21
4.21
0.73
20.62
19
3.23
1.71
0.56
13.1
3.24
2.3
0.56
13.11
3.47
2.94
0.6
14.77
3.82
3.58
0.66
17.42
4.25
4.21
0.73
20.95
20
-
-
-
-
4.31
2.35
0.74
21.39
4.27
2.93
0.74
21.07
4.36
3.53
0.75
21.91
4.59
4.15
0.79
23.76
6
15
0.89
0.89
0.13
0.91
2.07
2.07
0.3
4.52
2.74
2.74
0.39
7.24
3.37
3.37
0.48
10.25
3.96
3.96
0.57
13.45
17
0.89
0.89
0.13
0.91
2.07
2.07
0.3
4.53
2.74
2.74
0.4
7.25
3.37
3.37
0.49
10.27
3.97
3.97
0.57
13.48
19
2.03
1.28
0.29
4.36
2.49
2
0.36
6.13
2.96
2.68
0.43
8.25
3.45
3.35
0.5
10.7
3.98
3.97
0.57
13.53
20
-
-
-
-
3.36
2.01
0.48
10.17
3.5
2.63
0.5
10.93
3.8
3.28
0.55
12.51
4.18
3.92
0.6
14.74
13
3
15
1.71
1.71
0.49
10.48
2.31
2.31
0.67
17.67
2.9
2.9
0.83
25.79
3.47
3.47
1
35.4
4.07
4.07
1.18
46.79
17
1.75
1.73
0.5
10.91
2.32
2.32
0.67
17.71
2.9
2.9
0.83
25.85
3.47
3.47
1
35.48
4.06
4.06
1.18
46.9
19
3.13
1.67
0.9
29.34
3.1
2.25
0.89
28.79
3.24
2.87
0.93
31.1
3.56
3.49
1.02
36.65
4.08
4.08
1.18
46.97
20
-
-
-
-
4.15
2.29
1.2
48.29
4.11
2.87
1.19
47.57
4.12
3.46
1.19
47.81
4.31
4.06
1.24
51.65
4
15
1.41
1.41
0.3
4.58
2.06
2.06
0.44
8.8
2.67
2.67
0.57
13.56
3.27
3.27
0.7
19.14
3.85
3.85
0.83
25.4
17
1.4
1.4
0.3
4.59
2.06
2.06
0.45
8.82
2.67
2.67
0.57
13.59
3.27
3.27
0.7
19.18
3.85
3.85
0.83
25.46
19
2.23
1.35
0.48
10.02
2.44
1.99
0.53
11.69
2.81
2.64
0.6
14.81
3.29
3.28
0.71
19.32
3.86
3.86
0.83
25.53
20
-
-
-
-
3.32
1.99
0.71
19.69
3.36
2.6
0.72
20.08
3.6
3.22
0.77
22.68
3.96
3.84
0.85
26.64
5
15
0.68
0.68
0.12
0.8
1.75
1.75
0.3
4.51
2.41
2.41
0.41
7.75
3.02
3.02
0.52
11.42
3.62
3.62
0.62
15.53
17
0.68
0.68
0.12
0.8
1.75
1.75
0.3
4.52
2.41
2.41
0.41
7.77
3.03
3.03
0.52
11.45
3.62
3.62
0.62
15.57
19
1.29
0.97
0.24
3.01
1.87
1.71
0.32
5.06
2.45
2.4
0.42
7.98
3.03
3.02
0.52
11.46
3.63
3.63
0.62
15.61
20
-
-
-
-
2.38
1.67
0.41
7.59
2.76
2.33
0.47
9.75
3.19
2.99
0.55
12.47
3.66
3.63
0.63
15.83
6
15
0.54
0.54
0.08
0.51
0.89
0.89
0.13
0.88
2.1
2.1
0.3
4.52
2.76
2.76
0.4
7.21
3.38
3.38
0.49
10.15
17
0.54
0.54
0.08
0.51
0.89
0.89
0.13
0.88
2.1
2.1
0.3
4.53
2.77
2.77
0.4
7.23
3.39
3.39
0.49
10.18
19
0.54
0.53
0.08
0.51
0.89
0.89
0.13
0.88
2.11
2.1
0.3
4.53
2.77
2.77
0.4
7.24
3.39
3.39
0.49
10.2
20
-
-
-
-
1.37
1.25
0.22
2.49
2.24
2.07
0.32
5.06
2.82
2.76
0.41
7.47
3.4
3.39
0.49
10.22
15
3
15
1.06
1.06
0.3
4.58
1.71
1.71
0.49
10.29
2.32
2.32
0.67
17.3
2.91
2.91
0.84
25.96
3.51
3.51
1.01
35.55
17
1.06
1.06
0.3
4.59
1.71
1.71
0.49
10.31
2.32
2.32
0.67
17.34
2.92
2.92
0.84
26.02
3.51
3.51
1.01
35.64
19
1.29
1.02
0.37
6.33
1.77
1.7
0.51
10.95
2.32
2.31
0.67
17.32
2.92
2.92
0.85
26.09
3.51
3.51
1.01
35.74
20
-
-
-
-
2.31
1.65
0.66
17.21
2.56
2.28
0.74
20.86
2.97
2.93
0.86
26.67
3.5
3.5
1.02
35.78
4
15
0.48
0.48
0.1
0.67
1.42
1.42
0.31
4.58
2.07
2.07
0.45
8.79
2.68
2.68
0.58
13.64
3.27
3.27
0.71
19.2
17
0.48
0.48
0.1
0.67
1.42
1.42
0.31
4.59
2.07
2.07
0.45
8.81
2.68
2.68
0.58
13.67
3.28
3.28
0.71
19.25
19
0.48
0.48
0.1
0.67
1.42
1.41
0.31
4.59
2.08
2.08
0.45
8.83
2.69
2.69
0.58
13.71
3.28
3.28
0.71
19.3
20
-
-
-
-
1.63
1.37
0.35
5.82
2.15
2.05
0.47
9.36
2.69
2.69
0.58
13.72
3.28
3.28
0.71
19.32
5
15
0.33
0.33
0.06
0.36
0.69
0.69
0.12
0.77
1.78
1.78
0.31
4.63
2.43
2.43
0.42
7.83
3.04
3.04
0.53
11.47
17
0.33
0.33
0.06
0.36
0.69
0.69
0.12
0.78
1.78
1.78
0.31
4.64
2.43
2.43
0.42
7.84
3.04
3.04
0.53
11.49
19
0.33
0.33
0.06
0.36
0.69
0.69
0.12
0.78
1.78
1.78
0.31
4.65
2.43
2.43
0.42
7.86
3.05
3.05
0.53
11.52
20
-
-
-
-
0.69
0.69
0.12
0.78
1.79
1.79
0.31
4.67
2.44
2.43
0.42
7.87
3.05
3.05
0.53
11.54
6
15
-
-
-
-
0.54
0.54
0.08
0.49
0.9
0.9
0.13
0.86
2.13
2.13
0.31
4.6
2.78
2.78
0.4
7.2
17
-
-
-
-
0.54
0.54
0.08
0.49
0.9
0.9
0.13
0.86
2.14
2.14
0.31
4.61
2.79
2.79
0.4
7.21
19
-
-
-
-
0.54
0.54
0.08
0.49
0.9
0.9
0.13
0.86
2.14
2.14
0.31
4.62
2.79
2.79
0.4
7.23
20
-
-
-
-
0.54
0.54
0.08
0.49
0.91
0.91
0.13
0.86
2.14
2.14
0.31
4.63
2.79
2.79
0.4
7.24
Abbreviations:
EWT: Enter Water Temp. ()
Δt: Temperature Difference ()
DB: Dry Bulb Temp. ()
WF: Water Flow (m
3
/h)
WB: Wet Bulb Temp. ()
TC: Total Cooling Capacity (kW)
SC: Sensible Cooling Capacity (kW)
WPD: Water Pressure Drop (kPa)