Procedure
P5
Watersideheatexchangerwaterinlet/
outlettemperaturesensorisloose
1
Yes
Ensurethetemperaturesensoris
connectedproperly
No
Watersideheatexchangerwaterinlet/
outlettemperaturesensorhas
short‐circuitedorfailed
2
Yes
Replacethetemperaturesensor
No
Waterpipingcontainsair
Yes
Purgeairfromthewatersystem
2
No
Thewaterflowrateisnotsufficient,
causedbycrushedorbentwaterpiping,
incorrectpumpspeedsetting,high
resistanceinwaterpipingorbroken
expansionvessel
4
Yes
Inspectthesystemandfixtheerror
No
ReplacehydronicboxmainPCB
Notes:
1. WatersideheatexchangerwaterinlettemperaturesensorandwatersideheatexchangerwateroutlettemperaturesensorconnectionsareportCN6on
thehydronicboxmainPCB(labeled11inFigure4‐2.1inPart4,2.2"MainPCBforHydronicSystem").
2. Measuresensor resistance.If the resistanceis toolow, the sensorhasshort‐circuited.Iftheresistanceisnotconsistentwith thesensor’s resistance
characteristicstable,thesensorhasfailed.RefertoPart2,1.2“HydronicBoxLayout”andtoTable5‐5.3inPart5,5.1“TemperatureSensorResistance
Characteristics”.
3. RefertotheM‐ThermalSplitEngineeringDataBook,Part5,15“SPECIALFUNCTIONS”.
4. Checkwaterpressureonthemanometer.Ifthewaterpressureisnot>1bar,waterflowisinsufficient.RefertoFigures2‐1.7and2‐1.8inPart2,1.2
“HydronicBoxLayout”.