Installation
 Page 123 
water flows from the unit smoothly.
NOTE ON DRAIN HOSE  PLACEMENT:
• DO NOT kink the drain hose.
• DO NOT create a water trap.
• DO NOT put the end of drain hose in water or a 
container that will collect water.
Make sure there are no kinks or dent in drain hose to 
ensure proper drainage.
3.6  Connect signal cable
3.6.1  Before performing electrical work, read 
these regulations
1. All wiring must comply with local and national electrical 
codes, and must be installed by a licensed electrician.
2. All electrical connections must be made according to 
the Electrical Connection Diagram located on the panels of 
the indoor and outdoor units.
3. If there is a serious safety issue with the power supply, 
stop work immediately. Explain your reasoning to the 
client, and refuse to install the unit until the safety issue is 
properly resolved.
4. Power voltage should be within 90-110% of rated 
voltage. Insufficient power supply can cause malfunction, 
electrical shock, or fire.
5. If connecting power to fixed wiring, install a surge 
protector and main power switch with a capacity of 1.5 
times the maximum current of the unit.
6. If connecting power to fixed wiring, a switch or circuit 
breaker that disconnects all poles and has a contact 
separation of at least 1/8in (3mm) must be incorporated 
in the fixed wiring. The qualified technician must use an 
approved circuit breaker or switch.
7. Only connect the unit to an individual branch circuit 
outlet. Do not connect another appliance to that outlet.
8. Make sure to properly ground the air conditioner.
9. Every wire must be firmly connected. Loose wiring 
can cause the terminal to overheat, resulting in product 
malfunction and possible fire.
10. Do not let wires touch or rest against refrigerant 
tubing, the compressor, or any moving parts within the 
unit.
11. If the unit has an auxiliary electric heater, it must be 
installed at least 1 meter (40in) away from any combustible 
materials.
12. BEFORE PERFORMING ANY ELECTRICAL OR WIRING 
WORK, TURN OFF THE MAIN POWER TO THE SYSTEM.
3.6.2  Connect signal cable
The signal cable enables communication between the 
indoor and outdoor units. You must first choose the right 
cable size before preparing it for connection.
Cable Types:
• Indoor Power Cable  (if applicable): H05VV-F or 
H05V2V2-F
• Outdoor Power Cable: H07RN-F
• Signal Cable: H07RN-F
For Aurora series & Forest series:
1. Prepare the cable for connection:
• Using wire strippers, strip the rubber jacket from both 
ends of signal cable to reveal about 40mm (1.57in) of 
the wires inside. 
• Strip the insulation from the ends of the wires.
• Using wire crimper, crimp u-type lugs on the ends of 
the wires.
2. Open front panel of the indoor unit.
3. Using a screwdriver, open the wire box cover on the 
right side of the unit. This will reveal the terminal block.
Terminal block
Wire cover
Screw
Cable clamp
The Wiring Diagram is located 
on the inside of the indoor unit’s 
wire cover.
4. Unscrew the cable clamp below the terminal block and 
place it to the side.
5. Facing the back of the unit, remove the plastic panel on 
the bottom left-hand side.