Installation
 Page 131 
6.  Refrigerant Pipe Installation
6.1  Maximum length and drop height
Ensure that the length of the refrigerant pipe and the drop 
height between the indoor and outdoor units meets the 
requirements shown in the following table.
 M2OG-14HFN8-Q 
M2OC-18HFN8-Q, 
M2OD-18HFN8-Q
M3OE-27HFN8-Q, 
M3OF-27HFN8-Q 
M3OF-21HFN8-Q
M4OB-36HFN8-Q 
M4OE-28HFN8-Q
 M5OD-42HFN8-Q 
Max. length for 
all rooms
40 60 80 80
Max. length for 
one indoor unit
25 30 35 35
 Max. height 
different 
between IDU 
and ODU
15 15 15 15
Max. height 
different 
between IDUs
10 10 10 10
• When installing multiple indoor units with a single 
outdoor unit, ensure that the length of the refrigerant 
pipe and the drop height between the indoor and 
outdoor units meet the requirements illustrated in the 
following diagram:
Indoor unit   
Indoor unit   
Indoor unit   
Outdoor unit   
15m(49ft)
15m(49ft)
Max.Height difference
6.2  The procedure of connecting pipes
1.Choose the pipe size according to the specification table.
2.Confirm the cross way of the pipes.
3.Measure the necessary pipe length.
4.Cut the selected pipe with pipe cutter
 • Make the section flat and smooth.
 
l Ää áèì É
oçì ÖÜ
t ~ê éÉÇ
VM
5. Insulate the copper pipe
 • Before test operation, the joint parts should not be 
heat insulated.
6. Flare the pipe
 • Insert a flare nut into the pipe before flaring the 
pipe
 • According to the following table to flare the pipe.
Pipe diameter
(inch(mm))
Flare dimension A (mm/inch)  
Flare shape
Min Max
1/4" (6.35) 8.4/0.33 8.7/0.34
R0.4~0.8
4
5
°
±
2
90
°    
 
±
4
A
3/8" (9.52) 13.2/0.52 13.5/0.53
1/2" (12.7) 16.2/0.64 16.5/0.65
5/8" (15.9) 19.2/0.76 19.7/0.78
3/4" (19) 23.2/0.91 23.7/0.93
7/8" (22) 26.4/1.04 26.9/1.06
 • After flared the pipe, the opening part must be seal 
by end cover or adhesive tape to avoid duct or exog-
enous impurity come into the pipe.
7. Drill holes if the pipes need to pass the wall.
8. According to the field condition to bend the pipes so 
that it can pass the wall smoothly.
9. Bind and wrap the wire together with the insulated pipe 
if necessary.
10. Set the wall conduit
11. Set the supporter for the pipe.
12. Locate the pipe and fix it by supporter
 • For horizontal refrigerant pipe, the distance be-
tween supporters should not be exceed 1m.
 • For vertical refrigerant pipe, the distance between 
supporters should not be exceed 1.5m.
13. Connect the pipe to indoor unit and outdoor unit by 
using two spanners.
 • Be sure to use two spanners and proper torque to 
fasten the nut, too large torque will damage the