Installation
 Page 130 
Stow tube
 
•
Fill the water pan with 2 liters of water.
 
•
Check that the drainpipe is unhindered
.2.2 Units with a pump
1. Remove the test cover.
 
•
Fill the water pan with 2 liters of water.
Test cap
Stow tube
2. Turn on the unit in COOLING mode. You will hear 
the drain pump.Check whether the water is discharged 
properly (a 1-minute lag is possible, depending on the 
length of the drain pipe), Check whether water leaks from
the joints. 
3. Turn off the air conditioner and put the cap back on.
•  After turn off the air conditioner 3 minutes, check 
whether there is anything abnormal. If drainage 
pipes have not been distributed properly, over 
back-flow water shall cause the flashing of alarm 
indicator at remote-controlled receiving board and 
even water shall run over the water collector.
•  Continuously infusing water until water level 
alarmed, check whether the drainage pump could 
discharge water at once. If water level does not 
decline under warning water level 3 minutes 
later, it shall cause shutdown of unit. When this 
situation happens, the normal startup only can 
be recovered by turning down power supply and 
eliminating accumulated water.
Note: Drain plug at the main water-containing plate 
is used for eliminating accumulated water in water-
containing plate when maintaining air conditioner fault. 
During normal operation, the plug shall be filled in to 
prevent leakage.
5.4  Insulation work of drainage pipe
Refer the introduction to the insulation engineering 
parts.