EasyManuals Logo

Midea MCA3U-09HRFN1-M(C) User Manual

Midea MCA3U-09HRFN1-M(C)
247 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #67 background imageLoading...
Page #67 background image
64
E.Micro-switch SW6 is for selection of temperature compensation in heating mode. This helps to reduce
the real temperature difference between ceiling and floor so that the unit could run properly. If the unit is
on-floor installed, 0 should be chosen.
Range: 0
o
C, 2
o
C, 4
o
C, E function (reserved for special customizing)
F. Micro-switch S1 and dial-switch S2 are for address setting when you want to control this unit by a
central controller.
Range: 00-63
MUE-36HRFN1-M(C), MUE-48HRFN1-M(C)
A. Micro-switch SW1 is for selection of indoor fan stop temperature (TEL0) when it is in anti-cold wind
action in heating mode.
Range: 24
o
C, 15
o
C, Fan motor do not stop, According to EEROM setting (reserved for special
customizing).